2.
Technical data
Supply voltage
230 V AC 50 Hz
Power consumption
2.4 VA
Fuse
1.6 AT, microfuse 5 mm x 20 mm
Inputs
4 inputs:
temperature sensor: Pt1000 (-20 °C to +150 °C)
Outputs
2 electromechanical relays: each 1 A, 250 V AC (ε)
Protection degree
IP 20 as per DIN EN 60529 (VDE 0470-1)
Mode of operation
type 1 Y (as per DIN EN 60730-1)
Insulation class
2
Ambient temperature
0 °C to + 50 °C
Power reserve
> 10 years at + 20 °C, with lithium battery
Installation
wall-mounted
Housing
plastic, PC / ABS
Dimensions
170 mm x 170 mm x 55 mm
Weight
0.65 kg
Conformity
The solar controller meets the requirements of the Electromagnetic Compatibility
Directive (2004/108/EC), the Low Voltage Directive (2006/95/EC) and the har-
monised standards DIN EN 60730-1 and DIN EN 60730-2-9. It bears the CE
label.
3.
Safety instructions
DANGER
Danger of electrocution!
The controller is to be assembled, electrically installed, commissioned, inspected and repaired by
trained, competent and authorised persons (qualified electricians as per DIN VDE 1000-10 and
BGV A3) only!
Observe all applicable guidelines and regulations of the local electricity supplier!
Before beginning installation or repair work on electrical equipment, always ensure complete
disconnection from the mains and secure against reactivation!
Do not work on live parts!
The controller may only be installed and operated in:
dry environments which are not potentially explosive
closed rooms
rooms with a temperature between 0 °C and + 50 °C