3

24V/5V/ GND

Logic
Control
Circuit

PLC

AC equivalent circuit

inside the main module

S/S

X0

X

2

Xn

24Vdc

r

24V

COM

24V

Sensor

External provide

24Vdc

Power

24V

The I/O extension module internal equivalent sources and the input

signal wiring are shown below.

7.2 output characteristics and signal specifications

Output port specifications

Project

Transistor output port

External Power

5

24Vdc

Circuit isolation

PhotoCoupler

Operation indication

LED is on when optical coupler is driven

Leakage current of

open circuit

Less than 0.1mA/30Vdc

Minimum load

5mA

5

24Vdc

Max.

output

current

Resistive

load

Y0

Y7

0.3A/1 point

Others

0.3A/1 point

0.8A/4

point

1.2A/6 point

1.6A/8 point

Inductive

load

7.2W/24VDC

Lamp

load

Y0

Y7

0.9W/24Vdc

Others

1.5W/24Vdc

Response

time

ON

OFF Y0

Y7

Less than 5 us

Load current above 10 mA

Others

Less than 0.5ms

Load current above 100 mA

OFF

ON

Max output frequency

Y0

Y3

Each channel:200kHz

Y4

Y7

Each

channel:100kHz

Output common

terminal

Y0

Y1

COM0

Y2

Y3

COM1

Y4

Y5

COM2

Y6

Y7

COM3

Y10

Y13

COM4

Y14

Y17

COM5

Fuse protection

NO

8. Power operation and routine maintenance

8.1

Power operation

After the connection, item by item, check to ensure that no foreign

connections fall into the cabinet inside,heat flow

1

Switch on the POWER of the controller, POWER light should be light;

2

Start the PC software programming, Download the user program

will be programmed into the controller;

3

Download program calibration finished.

8.2

Routine Maintenance

Routine maintenance checking should pay attention to the following:

1

Ensure working environment clean and tidy, controller, avoid foreign

body in dust into machine;User equipment

2

To maintain good ventilation controller

3

All wiring connections and terminals, fixed tightly in good condition

4. Observe the indicator light controller, observe LCD display screen

and state information.

9. The common problems and solutions

When the controller can not work normally, please check in turn:
1. Power line connection and protection of electrical switches and

related conditions, ensure controller has been reliable power supply

2. The connection of user terminals is strong;
3. Refer to the fault record. If the above checks are done and when

confirmed controller still unable to work, Can refer to the table and

working status of the controller for analysis

Phenomenon

Possible cause

Solution

Power lights and other

lights are not bright

Power supply pressure loss

or voltage is too low

Check the power supply condition,

be ruled out

Disconnect the power
switch or fuse blown

Check the switch, wires or fuse

condition, be ruled out

Power wiring abnormal

Power board damage

Replace controller

POWER

Lights

flashing

Power lines contact

undesirable

Check and make sure

:1.24VL

24

VN terminal voltage whether

between the normal range;

2.

P24V and COM between

terminals whether short circuit or

load is too large

P24V/COM auxiliary

power output is circuit,

leading to the current limit

RUN indicator and

ALARM indicater are

not bright

Programme error

Confirm the power under normal

operation of the menu in controller

test

LCD can't display

properly

Power wiring undesirable,

or P24V/COM a short

circuit

Confirm the power under normal

operation of the menu in controller

test

Output cannot close

OFF

External connection is bad Re-wiring

make sure the eiring is

correct.

Relay contacts damage

Frequency movement of relay port

can be swapped with the port idle.

Can't download,

upload, monitoring

Programme cable connect

bad

Use the special programming

cable of Megmeet controller

A serial port can't

control the other

equipment

Cable connection bad, or

connection error, such as

the signal attribute TXD

and RXD confusion

Will signal lines connected

correctly

Communication master

and slave feature is

inconsistent,such as baud

rate,parity,data

bits,address.

The communation parameter is set

to the same.

Communication protocol is

inconsistent with the

master and slave

Set the same communation

protocal.

Notice

1. The warranty range is confined to the PLC only.
2.

Warranty period is 18 months

, within which period Megmeet

Network Power conducts free maintenance and repairing to the PLC

that has any fault or damage under the normal operation conditions.
3.

The start time of warranty period is the delivery date of the

product

, of which the product SN is the sole basis of judgment. PLC

without a product SN shall be regarded as out of warranty.
4. Even within 18 months, maintenance will also be charged in the

following situations:

Damages incurred to the PLC due to mis-operations, which are

not in compliance with the User Manual;

Damages incurred to the PLC due to fire, flood, abnormal voltage,

etc;

Damages incurred to the PLC due to the improper use of PLC

functions.

5. The service fee will be charged according to the actual costs. If there

is any contract, the contract prevails.