Megmeet MC100 Series Скачать руководство пользователя страница 2

2

Table 2-2 I/O extension module insulation specifications

Name

Test condition

User output (relay)
to extension bus

Capable of standing one minute of 2830Vac
(50Hz) or RMS current with no breakdown or
flashover. Leakage current ≤5mA

User input to user
output (relay)

Capable of standing one minute of 2830Vac
(50Hz) or RMS current with no breakdown or
flashover. Leakage current ≤5mA

User input terminal
and extension bus

Designed by following the SELV circuit
requirements

Table 2-3 I/O extension module power requirement

Model

5Vdc/GND

24Vdc/GND

24Vdc/COM

MC100-0800ENN

85mA

0

50mA

MC100-0808ERN

70mA

50mA

50mA

MC100-0808ETN

170mA

0

50mA

MC100-0008ERN

70mA

50mA

0

MC100-0008ETN

170mA

0

0

Note:
1. 5Vdc/GND: working power for logic circuit of extension module,
provided by the extension bus
2. 24Vdc/COM: input state detection power, through S/S terminal
3. 24Vdc/GND: working power for relay circuit of extension module,
provided by the extension bus

Before connecting the extension module to the basic module,
calculate the total current of all extension module circuits.
Make sure that the currents are smaller than the capacity of
the corresponding power supply at the basic module to avoid
overloading the basic module.

3 Input Features

3.1 Internal Equivalent Input Circuit

The extension module needs external power supply (+24Vdc)
for detecting user switch status. The internal equivalent
resistance of the input circuit is about 4.3kΩ, and
bi-directional photo coupler is used for signal detection. You
can use either sink mode or source mode, so long as dry
contact digital signal is input. To connect to the output of
active transistor sensor, you need to use the open collector
output mode. The wiring of I/O extension module internal
equivalent power and inputs is the same as those of the basic
module, as shown in Figure 3-1.

24V/5V/GND

Logic circuit work power 

from extension cable

Lo

gi

pr

oc

es

si

ng

 c

irc

ui

t

Extension module internal 

equivalent circuit

Sensor

To basic module

+24V

To basic module

COM

In

pu

t d

ev

ic

es

S/S

X0

X1

X2

Xn

External wiring

Figure 3-1 Internal equivalent input circuit

3.2 I/O Signal State Indicator

The input status indicator displays the status of input terminal.
The indicator turns on when the input is in the ON state.
Otherwise, the indicator is off.
The output status indicator displays the status of output
terminal. The indicator turns on when the output is in the ON
state (Yn is connected with COMn). Otherwise, the indicator
is off. See Figure 3-2.

Power indicator

Input status indicator

Output status indicator

Figure 3-2 Status indicator

4 Output Features

4.1 Relay Output Electric Specifications

Table 4-1 Relay output terminal electric specifications

Item

Relay output terminal

External power

Below 250Vac, 30Vdc

Circuit isolation

By relay

Operation indication

Relay output contacts closed, LED on

Leakage current of open
circuit

-

Min. load

2mA/5Vdc

Max.
output
current

Resistive load

2A/1 point, total current of 8 points
(sharing one COM) < 8A

Inductive load 220Vac, 80VA
Illumination

220Vac, 100W

Response
time

OFF

ON

Max.: 20ms

ON

OFF

Max.: 20ms

4.2 Transistor Output Electric Specifications

Table 4-2 Transistor output electric specifications

Item

Transistor output terminal

External power

5 ~ 24Vdc

Circuit isolation

Photo coupler

Operation indication

LED is on when photo coupler is driven

Leakage current of open
circuit

< 0.1mA/30Vdc

Min. load

5mA (5 ~ 24Vdc)

Max.
output
current

Resistive load

3A/1 point
8A/4 points
1.6A/8 points
Above 8 points, total current increases
0.1A at each point increase

Inductive load

24Vdc, 7.2W

Illumination

24Vdc, 1.5W

Respon
se time

OFF

ON

Max. 0.5ms (100mA/24Vdc)

ON

OFF

Max. 0.5ms (100mA/24Vdc)