USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
F - 22
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.8 Output configuration – admin
describes the SpeedSys300 ODS301 Modbus registers related to the module
output configuration – admin.
NOTE:
The Modbus registers in this data block are read/write.
Table F-13:
SpeedSys300 ODS301 Modbus registers – output configuration – admin
Address
Name
Data
type
Range
Access
Description
5500
rel1_config
uint16
Level 1
Relay 1 (SIL) status:
B0 – Latching
B1 – n.u.
B2 – Overspeed
B3 – Underspeed
B4 – Acceleration max.
B5 – Acceleration min.
B6 – n.u.
B7 – Proof test
B8 – Non-safety error.
5501
rel2_config
uint16
Level 1
Relay 2 (SIL) status:
B0 – Latching
B1 – n.u.
B2 – Overspeed
B3 – Underspeed
B4 – Acceleration max.
B5 – Acceleration min.
B6 – n.u.
B7 – Proof test
B8 – Non-safety error.
5502
rel3_config
uint16
Level 1
Relay 3 (non-SIL) status:
B0 – Latching
B1 – Inverted
B2 – Overspeed
B3 – Underspeed
B4 – Acceleration max.
B5 – Acceleration min.
B6 – Self diagnostics
B7 – Proof test
B8 – Non-safety error.
5503
rel4_config
uint16
Level 1
Relay 4 (non-SIL) status:
B0 – Latching
B1 – Inverted
B2 – Overspeed
B3 – Underspeed
B4 – Acceleration max.
B5 – Acceleration min.
B6 – Self diagnostics
B7 – Proof test
B8 – Non-safety error.