Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
F - 1
Status and diagnostics
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
APPENDIX F: SPEEDSYS300 ODS301
MODBUS REGISTER DEFINITIONS
This section provides an overview of the SpeedSys300 ODS301 Modbus register definitions
in a series of tables.
F.1 Status and diagnostics
F.1.1 Main status
describes the SpeedSys300 ODS301 Modbus registers related to
main status parameters.
NOTE:
The Modbus registers in this data block are read only.
Table F-1:
SpeedSys300 ODS301 Modbus registers – main status parameters
Address
Name
Data
type
Range
Access
Description
0000
device_ID
uint16
R/O
Device identification code.
SpeedSys300 ODS301 (SSY300 ID) is
2300.
0001
device_ver
uint16
R/O
Current firmware version
0002
ROM_CRC
uint16
R/O
Current program-ROM CRC
0003
pp_test_active
uint16
R/O
Proof test request active (digital input or
Modbus register). See also Modbus register
0112 (proof_req)).
0004
serial_num
uint16
R/O
Serial number.
Copy of “Device config - factory” serial
number.