USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
D - 6
I am changing/programming the configuration of my SpeedSys300 ODS301 mod
-
APPENDIX D: FREQUENTLY ASKED QUESTIONS (FAQ)
D.4 I am changing/programming the configuration of my SpeedSys300
ODS301 module but am not seeing the expected changes. What is
wrong?
To activate/change the configuration of a SpeedSys300 ODS301 module, the
Program device settings control in the overall module information and controls window is
used.
However, it is important to note that the SpeedSys300 ODS301 module and SpeedSys300
software must be operating at the Admin access level in order for the configuration to actually
be activated/changed.
The User access level is the default access level, so the SpeedSys300 ODS301 module and
SpeedSys300 software must be changed to the Admin access level before
activating/changing the configuration of a module
NOTE:
Activating a configuration on SpeedSys300 ODS301 module (that is, programming
the module) is only possible when the SpeedSys300 ODS301 module and
SpeedSys300 software are operating at the Admin access level.
If the SpeedSys300 ODS301 module and SpeedSys300 software are operating at the User
access level when the Program device settings control is used, the software/system can give
the impression that the module’s configuration has been updated, but it will not be.
See
for further information.
At any time, the Read device settings control in the overall module information and controls
window can be used to download the configuration from a module, that is, to check the actual
configuration running on a module.