d.
To change the settings of the TTR place the mouse on the form and
right-click. Then select “TTR Settings”.
e.
This dialog box allows you to change the TTR settings. The settings
that can be changed are as follows:
1.
Show Diagram Number
When enabled this will display a numeric field below the
winding configuration diagram on the form. The diagram
can then be changed by entering a number in this field.
2.
Standard
This enables you to choose between the ANSI, Australian, or
IEC Standard.
3.
Test Voltage
This enables you to choose the test voltage at which the test
is run. Auto allows the instrument to choose an acceptable
test voltage for testing. You may choose between Auto, 8,
40, or 80.
4. Running an Automated Test
a.
Select the Initialize Instrument button.
b.
Automated fields should now turn cyan colored.
c.
Right-click on the cyan colored fields.
d.
Follow the on screen instructions specific to the test.