1 INTRODucTION  

I

ntroduction  

1.1 Product description

The MTO106 transformer ohmmeter is an easy-to-use, 
line-operated instrument specifically designed for safe 
and accurate field measurement of winding resistance 
in smaller transmission and distribution transformers.
It has dual channels with a wide measurement range 
and can accurately provide information about the 
vast majority of power transformers, reactors and 
instrument transformers. The test current can be 
manually set in five different ranges to fit transformers 
of various sizes. 
The unit has built-in safety protection for testing 
transformers and other components with high 
inductance. To ensure operator safety, MTO 106 
automatically discharges the stored energy in the 
transformer at the end of each test. If a current lead 
is disconnected while current is flowing through 
the transformer, the current will flow through the 
alternate path of the potential lead without damage 
to the instrument or risk to the operator

Features and benefits

 

Test current up to 6 A and stable current generation

 

up to 48 V output voltage for fast charging of 
transformer windings

 

Light weight and portable

 

Very short start-up time

 

Ease of use

 

Resistance range, 10 µOhm to 30 kOhm, for testing a 
wide variety of transformers.

Applications

The MTO106 is mainly intended for field 
measurements of smaller transmission and distribution 
transformers:

 

To verify factory test readings

 

As part of a regular maintenance program.

 

To help locate the presence of defects in transformers 
such as increased contact resistance in terminal 
connections and tap changers.

The instrument can also be used for general resistance 
measurements of for instance control wiring, voltage 
regulators, motors, generators and all types of 
connections.

1.2 Winding resistance 
testing 

Transformer winding resistances are measured in 
the field in order to check for abnormalities due to 
loose connections, broken strands, and high-contact 
resistance in tap changers. Interpretation of results is 
usually based  on  a  comparison  of  measurements 
made separately  on  each  phase  in  the  case  of  a  
wye-connected winding or between pairs of terminals 
on a delta-connected winding. comparison may also 
be made with original data measured in the factory.
Winding resistance measurements in transformers 
are of fundamental importance for the following 
purposes:

 

calculations of the I

2

R component of conductor losses.

 

calculation of winding temperature at the end of a 
temperature test cycle.

 

As a diagnostic tool for assessing possible damage in the 
field.

Problems or faults occur due to poor design, assembly, 
handing, poor environments, overloading or poor 
maintenance. Measuring the resistance of the 
windings assures that the connections are correct and 
the resistance measurements indicate that there are 
no severe mismatches or opens. Many transformers 
have taps built into them. These taps allow ratio to be 
increased or decreased by. Any of the ratio changes 
involve a mechanical movement of a contact from one 
position to another. To tetect contact wear, winding 
resistance measurements are usually performed at 
each tap in a load tap changer.

Содержание MTO106

Страница 1: ...WWW MEGGER COM User s Manual Art No ZP BN01E Doc BN034794AE V01a 2018 MTO106 Transformer ohmmeter...

Страница 2: ......

Страница 3: ...iptions or software listings that disclose source code are for informational purposes only Reproduction in whole or in part to create working hardware or software for other than Megger Sweden AB produ...

Страница 4: ...enance 9 3 Instrument description and Accessories 10 3 1 Panel 10 3 2 The display 11 3 3 Accessories 11 Included 11 Optional 11 4 Setup and operation 12 4 1 Preparations 12 4 2 Testing Single and Dual...

Страница 5: ...BN034794AE ZP BN01E MTO106 5...

Страница 6: ...program To help locate the presence of defects in transformers such as increased contact resistance in terminal connections and tap changers The instrument can also be used for general resistance mea...

Страница 7: ...lowing shipment Our liability is specifically limited to replacing or repairing at our option defective equipment This warranty does not include batteries lamps or other expendable items where the ori...

Страница 8: ...ground pin Do not defeat the safety ground in any manner The equipment must be connected to a grounded mains outlet 3 Ground lead The first connection made and last removed is the connection of instr...

Страница 9: ...that are not intended for use together with the instrument Maintenance 1 DISCONNECT the MAINS plug before any cleaning or maintenance 2 Refer all servicing to Megger authorized personnel Do not attem...

Страница 10: ...display 5 DISCHARGE Built in discharge circuit safely discharges the test object when test is completed LED and audio sig nal indicate the charging status 6 100 240V 5A 50 60Hz Mains input and fuse bo...

Страница 11: ...proach 100 only very slowly Note If dual channel measurement is selected the above values are duplicated 3 3 Accessories Included Test lead black with banana connector and Kelvin clamp 10m 33ft 1 GC 3...

Страница 12: ...current switch is set to OFF 2 Connect the Kelvin type test leads to the MTO106 see figures below The leads marked Generator to the CUR RENT OUTPUT terminals of corresponding colour and the leads mark...

Страница 13: ...e indication of discharging 4 3 Testing Delta winding resistance Testing Delta winding resistance may be a very time consuming procedure in particular LV winding deltas The correct balance time can ta...

Страница 14: ...with only small deviations between different tap position changes Fig 1 shows a typical behavior for a transformer tap changer in as new condition Fig 5 1 Winding resistance vs tap position for a new...

Страница 15: ...cording to the method below 1 Run a normal winding resistance test accord ing to the instructions in section 4 2 Testing Single and Dual windings on page 12 2 Swap the terminals preferably by swapping...

Страница 16: ...leads switched 3 Sense leads not connected 4 Current leads shorted 1 Increase test current 2 Check sense leads 3 Check sense leads 4 Check current leads U 0 06 mV 0 0 A No current loop current leads n...

Страница 17: ...BN034794AE ZP BN01E MTO106 17 7 Specifications...

Страница 18: ...mensions W x D x H 360 x 304 x 194 mm 14 2 x12 x 7 6 Weight 7 3 kg 16 lbs excl cables Display 4 inch backlit monochrome alphanumerical display Test leads 2 x 10 m 33 ft with banana connectors and Kelv...

Страница 19: ......

Страница 20: ...Equipment Fiber Optic Test Equipment Ground Resistance Test Equipment Insulation Power Factor C DF Test Equipment Insulation Resistance Test Equipment Line Testing Equipment Low Resistance Ohmmeters...

Отзывы: