5.2.3 No-trip loop testing using the RED/GREEN test leads 

The [No-Trip] loop test can be carried out where a power socket is not available using the 2 wire lead set.

 

 
5.2.3.1 Phase to earth loop test  

1.

 

Select the [No Trip] test range on the lower range knob, and [Z] on the upper range knob where present. 

2.

 

Connect the RED and GREEN test leads to the instrument. 

3.

 

Connect the RED test lead to the 

Phase

 conductor and connect the GREEN test lead to the 

Earth

 

conductor. 

4.

 

The loop test will automatically start and the [

] symbol will appear, and remain on, for the duration 

of the test. 

5.

 

After a test period of 10 seconds the measured loop value is displayed.  

6.

 

To repeat the loop test, press the [

TEST

] key. 

 

The symbols [

] and [

] may appear during the test. Refer to section 5.1.1.2 (Symbols) for an explanation of 

their meaning. 

 

5.2.3.2 Phase to Neutral and Phase to Phase loop testing 

Both Phase to Neutral and Phase to Phase testing can be made using the No-Trip test, as described above for the 
Phase to earth test. However a High current test will not trip RCDs when making either a P-N or P-P test, and it is 
recommended that a High current test is used for both these measurements. 

 

5.2.4 Earth bonded metalwork testing 

Repeat the test 5.2.3.1 (Phase to Earth) test above, but with the GREEN lead connected to the exposed 
metalwork providing the earth return path. 

 

5.3 High current loop test [High Current] 

The [

High Current

] loop test performs a 2-wire high current test at around 4 A on a 230 V supply, providing a 

very stable and fast loop test.  
 

WARNING: This test is designed for non-RCD protected circuits.   
Due to the high currents used the instrument adds a brief pause between tests to prevent 

overheating. This is indicated by the [ 

] symbol and appears for a nominal 5 seconds between 

tests for voltages <260 V and 10 seconds for voltages above 260 V.

 

 

5.3.1 High current Phase to Earth loop test 

1.

 

Select the [

High Current

] test range on the lower range knob, and [Z] on the upper range knob where 

present. 

7.

 

Connect the RED and GREEN test leads to the instrument. 

8.

 

Connect the RED test lead to the 

Phase

 conductor. 

9.

 

Connect the GREEN test lead to 

Earth

 conductor. 

This test can also be performed using the mains socket test lead, using the RED and GREEN connectors). 

10.

 

The loop test will automatically start and the [

] symbol will appear, and remain on, for the duration 

of the test. 

11.

 

The measured loop value is displayed. 

 

Note: The AUTO START function will not operate if the instrument is connected to a live supply BEFORE the 
range knob is moved to [High Current]. This is to prevent tripping of RCDs by accidentally selecting the [High 
Current] test instead of [No Trip] test, with the leads connected to the supply. In which case pressing the [TEST] 
button will start a test. 
Subsequent connection of test leads will run the AUTO START test. 
 
AUTO START can be disabled in the SETUP procedure as described in section 8. 

 

5.3.2 High current Phase to Neutral loop test 

Repeat test 5.3.1 with the Green lead connected to the Neutral conductor. 

This test can also be performed using the mains socket test lead, using the RED and BLUE connectors. 

 

5.3.3 High current Phase to Phase loop test 

Repeat test 5.3.1 with the Green lead connected to another phase conductor. 

 

Содержание LTW315

Страница 1: ...M LTW300 Series Earth Loop testers User Guide...

Страница 2: ...lace whilst conducting tests Test leads probes and crocodile clips must be in good order clean and with no broken or cracked insulation On test leads fitted with a outlet plug and flying leads never c...

Страница 3: ...oop test 14 High current Phase to Neutral loop test 14 High current Phase to Phase loop test 15 High resolution loop test LTW425 only 15 Prospective fault current display PFC 15 PFC measurement 15 Pos...

Страница 4: ...nings and instructions before attempting to use the instruments This user guide describes the operation and functions of the following LTW300 series of loop impedance testers LTW315 LTW325 LTW335 LTW4...

Страница 5: ...d return it to Megger as soon as possible to help us reduce any delays in supporting you should the need arise Carton contents for the LTW315 LTW325 LTW335 and LTW425 1 x LTW series loop tester 1 x 2...

Страница 6: ...sults Fuse Blown Refer to User manual Battery status Ranges Supply noise warning R1 R2 Function selected Zref function selected required before R1 R2 can be measured Loop test active Temperature warni...

Страница 7: ...n Backlight On Off Test lead connections See section 2 5 Loop test function all except LTW315 Z MaxZ R1 R2 Zref Neck strap slots Range selector NO TRIP High Current HIGH Res LTW425 Volts Frequency Set...

Страница 8: ...ntrols OK Confirms a test result delete request ESC Aborts a result save process UP DOWN arrows Scrolls through circuit and distribution board numbers STORE Stores last test result LAST As next NEXT S...

Страница 9: ...ifting up front panel tab 1 2 Foldaway underneath instrument 2 3 and push into retaining slot 4 Single or 3 Phase connection Earth Neutral or 2nd phase connection Warning Read user guide Maximum 300V...

Страница 10: ...ssist drying 4 General operating instructions 4 1 Backlight operation Pressing the BACKLIGHT button will toggle the backlight on and off The backlight will automatically switch on at the start and end...

Страница 11: ...zardous in a live socket outlet 4 3 Test lead connection The supplied test leads should be connected to the appropriate sockets on the rear of the instrument marked L0 L2 and L1 Standard test probes a...

Страница 12: ...the noise symbol is displayed at the end of a test the test should be repeated or the test mode changed to mode 2 refer to section 8 SETUP procedure Mode 2 AUTO Default setting In Mode 2 the LTW loop...

Страница 13: ...5 IS NOT RATED FOR PHASE TO PHASE MEASUREMENTS ON 240 VOLTS TO EARTH SYSTEMS 5 2 Performing a loop test Note Factory settings for the instrument are AUTO START enabled Mode 2 extended testing enabled...

Страница 14: ...fast loop test WARNING This test is designed for non RCD protected circuits Due to the high currents used the instrument adds a brief pause between tests to prevent overheating This is indicated by th...

Страница 15: ...nt display PFC NOTES The PSCC of a circuit is the largest Prospective Fault Current PFC In a single phase system this would be the larger of the earth loop PFC and the neutral loop PSCC In a multi pha...

Страница 16: ...ortion of reactance in the measurement Worst case operating error calculated for Non Trip measurement mode in accordance with IEC 61557 3 1997 Intrinsic error or influence quantity Reference condition...

Страница 17: ...ted 6 All subsequent loop test measurements will have the Zref resistance subtracted 7 To view the stored value of Zref press the PFC key press the PFC again to return to the R1 R2 value 8 If measured...

Страница 18: ...Record number Each test result is assigned a unique record number from 0 to 999 logged automatically This cannot be changed by the user 7 2 To store a result 1 Make a Z MaxZ Zref or R1 R2 loop measure...

Страница 19: ...nload from the software tool bar 4 Connect the tester to the PC using the USB download lead 5 Set the lower range knob to SEND 6 The instrument will automatically download its contents to the PC A bar...

Страница 20: ...the function 4 Press the key to cycle through the options available for that function Once the desired option is displayed press TEST to store setting The display will show Ok and then return to the...

Страница 21: ...Press the TEST button to store the offset The display will show Ok to confirm setting has been saved 15 The display will show the as a reminder to warn of there is a loop resistance offset selected To...

Страница 22: ...ing test Retest or investigate source of noise Instrument needs calibration Further testing is possible but not recommended Noise symbol displayed at end of test indicates result may have been adverse...

Страница 23: ...possible until batteries have been replaced Note NiMH rechargeable batteries show a lower charge than Alkaline batteries and may not give much warning before becoming exhausted Faulty stuck key or sw...

Страница 24: ...n unused for an extended period 10 3 Fuse Blown indication If the fuse has blown after contact with a live supply the fuse blown symbol and the UnS message will be displayed and the instrument will st...

Страница 25: ...0 03 100 V a c and 300 V a c LTW325 and LTW425 10 0 02 LTW425 15 0 03 50 V a c LTW325 LTW335 and LTW425 Nominal test current No Trip loop test 15 mA at nominal 230 V a c supply High current loop test...

Страница 26: ...rdance with IEC61326 1 Operational uncertainties Refer to www megger com Power supply Battery 8 x 1 5 V cells IEC LR6 type AA alkaline Rechargeable 8 x 1 2V NiMH cells Battery life 2000 consecutive te...

Страница 27: ...ted by a worldwide network of approved repair and calibration companies which offer excellent in service care for your Megger products Returning your product to Megger UK and USA service centres 1 Whe...

Страница 28: ...com Megger Pty Limited Unit 26 9 Hudson Avenue Castle Hill Sydney NSW 2125 Australia T 61 0 2 9659 2005 F 61 0 2 9659 2201 E ausales megger com Megger Limited 110 Milner Avenue Unit 1 Scarborough Ont...

Отзывы: