Megger ICLAMP Скачать руководство пользователя страница 2

3. Close the ICLAMP around the conductor 

under test.

4. Set the rotary selector switch to the

A

position.

5. The ground current flowing in the 

conductor will be displayed.

Resistance measurement using ART

1. Ensure the rotary selector switch is in the 

position.

2. Connect the instrument as shown.

3. Close the ICLAMP around the conductor 

under test.

4. Set the rotary selector switch to the 3P 

or 4P                position.

5. Press and release the 

button [by 

holding the 

button, the resistance 

measurement will be continually updated].

6. The instrument will perform pre-measure-

ment checks, the status of which will be 
indicated on the display.

7. The three-terminal or four-terminal 

resistance reading using ART will be dis-
played.

SPECIFICATIONS

Measurement range:

1 mA to 1200 A

Transformation ratio

: 1000 : 1

Output signal: 

1 mA / A (1 A @ 1000 A)

Accuracy

1mA to 100 mA : 

3% of reading

0.1 A to 1 A : 

2% of reading

1 A to 10 A : 

1% of reading

10 A to 100 A : 

0.5% of reading

Operating temperature

-10°C to +50°C / 14°F to 122°F
0% to 85% RH at +35°C / 95°F

Storage temperature

-20°C to +70°C / -4°F to 158°F

Jaw opening:

57 mm maximum  (2.3 in)

Maximum conductor size:

52 mm (2.1 in)

Insulation:

Double insulation

Voltage rating:

600 V CAT III

Current rating:

1200 A for 20 minutes

Ingress protection:

IP40

Safety

EN61010-2-032

EMC 

EN 50081-1 Class B

EN 50082-2

Dimensions: 

111 mm x 216 mm x 45 mm 

(4.4 in x 8.5 in x 1.8 in)

Weight:

0.5 kg approximately (1.2lb)

TEST

TEST

OFF

PREPARATIONS FOR USE

1. Ensure that the ICLAMP jaw mating surfaces

are free of dust and contamination and that 
they contact completely when the ICLAMP 
is closed.

2. Currents carried by conductors in close 

proximity to the ICLAMP may affect 
calibration and reduce the accuracy of 
measurements made.

CALIBRATION OF THE ICLAMP

The ICLAMP should be calibrated once at
each test site to take into account the effects
of transportation, temperature and humidity
on the ICLAMP.
1. Ensure the rotary selector switch is in the

position.

2. Connect the instrument as shown.3.

Connect the C1 and C2 terminals together
using the calibration lead supplied with the 
ICLAMP [X and C terminals for DET3TC].
4. Ensure that the ICLAMP is not clamped 

around a conductor.

5. Press and hold the 

button and 

switch instrument ON to the                

A

setting using the selector switch.

6. Release the 

button.

7. Press and hold the 

button until a “0” 

reading is obtained on the display

8. Close the ICLAMP around the calibration 

lead which connects the C1 and C2 
terminals [X and C terminals for DET3TC].

9. Press and hold the 

button until a 

“100” reading is obtained on the display.

10. Switch the instrument 

using the 

selector switch.

11. The instrument is now calibrated to the 

ICLAMP and the calibration stored in non-
volatile memory. 

OPERATION OF THE ICLAMP

Measurement of ground current

1. Ensure the rotary selector switch is in the 

position.

2. Connect the instrument as shown.

OFF

OFF

TEST

TEST

TEST

TEST

OFF

ICLAMP

ICLAMP

Electrode

under test

ICLAMP

Installation

earthing

conductor

Potential spike

Electrode

under test

3 terminal

lead null

Current spike

DET4TC
DET4TCR

DET4TC
DET4TCR

DET4TC
DET4TCR

DET4TC
DET4TCR

Отзывы: