Check whether refrigerant circuit is unblocked
1. IDU’s coil of EXV is abnormal?
2. IDU’s EXV is abnormal, through monitoring
software to check the EXV’s open degree
3. IDU’s EXV is dirty block?
Yes
→
1. Replace power coil of EXV
2. Replace EXV
↓
Contact the manufacturer's Technician
5.2 F8 Error code
F8
:
Compression ratio too high protection
When detect the
pd / ps
>
8
,
then system begin to slow down the compressor
running frequency . After the frequency was down to the lowest value and detected the
pd/ps
>
8
all the time
within 400s
. Then will appear F8 Error code, whole system stop
running.
※
pd: High pressure value ps: Low pressure value
↓
Stop valve is OFF?
→
Open
NO
↓
Condenser and evaporator dirty block?
→
Clean
NO
↓
Pipe is flattened?
→
Re welding
NO
↓
Heating EXV is abnormal? Through check the
→
Replace EXV
Содержание ARV Series
Страница 4: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual Part1 Refrigerant Circuit...
Страница 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Страница 75: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 75 click Next 5 Confirm click Install...
Страница 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Страница 92: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 92 4 Operation Parameter Information...
Страница 108: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 108 5 Input the Register and finish...
Страница 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Страница 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Страница 119: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 119 Part4 Special Control...
Страница 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Страница 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Страница 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Страница 152: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 152 TSRN TR IN NO2 CH2 4WV1 SV1 SV3 SV5 SV6...
Страница 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...