background image

15 

00241 

messages

 

SEC-B 

Test fail check all appliances: 

The system has found an escape of gas, the most common cause is an open appliance. Check all appliances are off and restart 
the pressure test. If the system still reports test fail then a leak will be on the pipe work. Using “Blind button A” (see page 2) you 
can view the gas pressures at the valve, the outlet pressure must remain at least 90% of the value of the inlet pressure or a leak 
will be declared. 
 

Error from valve sender unit

 

System is not receiving data from the sender unit. The pressure sender is a required part of the system and cannot be “linked 
out”. Verify the sender is correctly wired and that you have a green flashing LED on the sender unit. 
 

Detector fault XX 

The system believes it has lost connection to a detector on address XX, verify detector addresses and press the “learn 
button” 

(23)

. Verify all connected detectors are being registered by pressing “blind button B” (see page 2). If you have no 

detectors connected to the system pressing the learn button will clear the error message. 
 

Supply and/or Extract fans not running. 

The system can monitor the fan status via a current monitor or air pressure switches. These provide a closed contact to 
terminals S1 and E1, it is a requirement when using fan interlocking that the fans be running (and therefore the S1 and E1 
receiving a closed contact) before the system can begin a gas pressure test. If at any point the fans stop running (opening the S1 
or E1 contact) the system will isolate the gas and report fans not running. Check that the fans are not only switched on, but 
actually running and moving air. 
 

Low incoming gas pressure. 

The system requires a minimum of 13 mBar of pressure at the inlet side of the gas valve, this is to ensure a correct strength 
flame. If at any time the incoming pressure drops below 13mBar for more than 10 seconds the system will isolate the gas and 
report “low incoming gas pressure” 
Note: if this occurs during installation check the sender unit direction of flow, if the sender is installed backwards the system will 
believe the “outlet” to be the “inlet” and therefore see an open end as being low incoming gas pressure. 
 

Emergency stop button pressed. 

The system has an panel mounted emergency stop and connection inside for remote buttons. First check the panel button (once 
pressed some require resetting by twisting and releasing). Clear the message by turning the main system switch off and then 
back on, if the message remains check any remote buttons and their connections. The terminal for the remote buttons requires 
a volt free normally closed contact, ensure all remote stop buttons, thermal links any another connected systems (BMS/Fire 
panels) are reset and the contacts are closed. 

In the event of any alert the system will always give a reason on screen as to the cause. 

 
Common messages you may receive are shown below with further explanation. 
If you require any help or if anything is unclear then please contact technical support on 0161 233 0600 

 

 

Содержание SEC-B

Страница 1: ...ent that this safety system is installed and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation o...

Страница 2: ...uttons A and B for engineer functions LED indications Power On green A blind button for displaying gas pressures on the LCD screen Gas Electric red when active to warn of live service Fans running lig...

Страница 3: ...s 70 mbar OPTB Auto Restart on power failure and fire alarm activation off by default SP 2 minute delay to the auto restart this enables downstream appliances or flame failure devices to close 17 Fill...

Страница 4: ...as detectors 1 8 press A B together to view 9 16 Fire Test Mode Press button B three times When connected to a fire alarm panel using the fire alarm terminal no 13 the system will isolate the gas duri...

Страница 5: ...1 Option Headers 18 19 21 20 Fan comm To enable the commissioning of the gas portion of the system before the ventilation interlock is completed you may temporarily disable the interlocking by pressin...

Страница 6: ...e the gas detectors own instructions for more guidance SEC B Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one...

Страница 7: ...een 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional information or...

Страница 8: ...nnect in parrallel Live feed through the Medem CM2M K2 channel current Monitor fans Fan speed controls Fan live Supply Fire Alarm Requires a volt free NC contact Where using 3 phase fans interlock on...

Страница 9: ...sent within the panel IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds Contactor coil Live feed through switched relay To...

Страница 10: ...s fitted the correct way round Note there is no flow through the pressure sender unit it is purely reading the pressures either side of the valve Correct Pressur e Solenoid Never mount the valve such...

Страница 11: ...Solenoid coil of the valve should never be mounted below the horizontal Pressure sender unit should never be mounted upside down to protect from water ingress Approx 400mm length INLET PORT OUTLET PO...

Страница 12: ...d be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicato...

Страница 13: ...er Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry...

Страница 14: ...n the LCD display that all the detectors have been recognised by the panel A recognised detector will appear as CO Carbon Monoxide CM combustible CH Carbon Dioxide OX Oxygen depletion and TP Temperatu...

Страница 15: ...sure test If at any point the fans stop running opening the S1 or E1 contact the system will isolate the gas and report fans not running Check that the fans are not only switched on but actually runni...

Отзывы: