background image

5

105750

OWNER’S MANUAL

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr  the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_________________ Btu/Hr

Gas water heater*

_________________ Btu/Hr

Gas furnace

_________________ Btu/Hr

Vented gas heater

_________________ Btu/Hr

Gas fireplace logs

_________________ Btu/Hr

Other gas appliances*

+ _________________ Btu/Hr

Total

= _________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Total

=

60,000

Btu/Hr

Continued

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Содержание MBP20TLB

Страница 1: ...taller service agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer Heater Sizes 20 000 Btu Hr Thermostat and 30 000 Btu Hr Thermostat Model Heaters Save this manual for future reference WARNING Improper installa tion adjustmen...

Страница 2: ...vehicle where curtains furniture clothing or other flammable objects are less than 36 inches from the front top or sides of the heater as a fireplace insert in high traffic areas in windy or drafty area 6 This heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensor ODS pi lot light safety system The ODS shuts down the heater if not enough fresh air is...

Страница 3: ...eater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater PRODUCT FEATURES SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensor Shutoff System ODS TheODS pilotisarequiredfeatureforvent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piez...

Страница 4: ...municating only iftherearedoorlesspassagewaysorventila tion grills between them PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANS Z223 1 Sec tion5 3 AirforCombustionandVentilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusually Tight Construction 2 Unconfined Space 3 Confined Space The information on p...

Страница 5: ...direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 60 000 Btu Hr actual amount of Btu Hr used The...

Страница 6: ...Figure 2 Ventilation Air from Inside Building WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Figure 3 Ventilation Air from Outdoors Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of th...

Страница 7: ... heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as to bacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may discolor walls NOTICE This heater is intended foruseassupplementalheat Use this heater along with your pri mary...

Страница 8: ...es apart from their centers Attach mounting bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Removing Front Panel Of Heater 1 Remove two screws near bottom cor ners of front panel 2 Liftstraightupongrillguarduntilitstops Grill guard will slide up about 1 4 3 Pull bottom of front panel forward then downward 4 Remove cardboard packing from grill and glass Attach...

Страница 9: ...il mounting bracket is firmly fastened to wall Placing Heater On Mounting Figure 9 Folding Anchor INSTALLATION Continued Figure 10 Popping Open Anchor Wings For Thin Walls Stand Out Tab Figure 11 Mounting Heater Onto Mounting Bracket Figure 12 Installing Bottom Mounting Screws Horizontal Slots Mounting Bracket attached to wall Bracket 1 Locate two horizontal slots on back panel of heater 2 Place h...

Страница 10: ...trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly CAUTION Never connect heater directly to the propane LP supply This heater requires an external regulator not supplied Install the external regulator be tween the heater ...

Страница 11: ... pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Foll...

Страница 12: ...g pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 This heater has a safety interlock system Wait one 1 minute before lighting pilot again 8 Turn control knob counterclockwise C clockwise to desired heating level The main burner should light Set control knob to any heat level between HI and LO TO TURN OFF GAS TO APPLIANCE Shutting Off Heater 1 Turn contro...

Страница 13: ...TENANCE CABINET Air Passageways Use a vacuum cleaner or pressurized air to clean Exterior Use a soft cloth dampened with a mild soap and water mixture Wipe the cabi net to remove dust WARNING Turn off heater and let cool before cleaning CAUTION You must keep control areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearl...

Страница 14: ...e following A Low gas pressure B Dirty or partially clogged ODS pilot 7 Thermocouple damaged 8 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabinet Nut is located inside heater cabinet at top 6 Replace ignitor cable 7 Replace piez...

Страница 15: ...e page 13 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clear ances see Figure 4 page 7 4 Clean burner see Cleaning and Mainte nance page 13 or replace burner orifice 1 Turn...

Страница 16: ...essive contact qualified ser vice person 1 Ventilate room Stop using odor caus ing products while heater is running 2 Locate and correct all leaks see Check ing Gas Connections page 11 1 Open window and or door for ventilation 2 Contact local propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 13 1 Locate and correct all leaks see Check ing Gas Connections page 11 2 Replace ...

Страница 17: ...o return the defec tive part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can t supply original replacement part s call Cans Unlimited Incorporated s Parts Department at 1 800 922 7407 for referral information WhencallingCansUnlimitedIncorporated have ready model number of your heater the replacement part number ACCESSORIES MANUAL SHUTOFF VALVE GA5010 ...

Страница 18: ...18 105750 BLUE FLAME PROPANE LP HEATER 11 1 11 2 MBP20TLB MBP30TLB ILLUSTRATED PARTS BREAKDOWN 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 16 18 19 20 21 22 15 23 24 17 7 ...

Страница 19: ...9 098271 03 098271 03 Ignitor Cable 1 10 098249 01 098249 01 Nut M5 2 11 099440 06 099440 06 Pilot Service Kit 1 11 1 098514 01 098514 01 Thermocouple 1 11 2 098594 01 098594 01 Ignitor Electrode 1 12 103446 01 103447 01 Burner 1 13 099387 03 099387 03 3 16 Pilot Tubing 1 14 103845 05 103845 07 Injector 1 15 099066 01 099066 01 Mounting Bracket 1 16 099415 06 099415 06 Pressure Regulator 1 17 0995...

Страница 20: ...the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of ...

Отзывы: