DIGITAL CLAMP METER

MODEL : 

27-AUTO/27T-AUTO

INSTRUCTION  MANUAL

®

1

4

Temperature (27T-AUTO only)

Range

: -20

0

C to 750

0

C

-4

0

F to 1400

0

F

Accuracy

: ± (3% rdg + 5 dgts)

Resolution

: 1

0

C / 1

0

F

Sensor

: K type thermocouple

2. OPERATION

Before taking any measurements, read the safety information section.
Always examine  the instrument for damage, contamination (excessive
dirt,  grease, etc.) and defects. Examine the test leads for cracked or
frayed insulation. If any abnormal conditions exist do not attempt to
make any measurements.

AUTO POWER OFF (APO)

The meter will be switch off if no range switch or key is used for approx
15 minutes.

FUNCTION BUTTON

The Button is used for select 

 /    range and 

0

C/

0

F (27T-AUTO only)

HOLD BUTTON

Press Hold button to toggle in and out of Hold mode, In the Hold mode,
the “ H ” annunciator is displayed.

MAX BUTTON

Press MAX button to toggle in and out of MAX mode (holding the highest
absolute reading) In the MAX mode, the “ MAX ” annunciator is displayed.
This function is available for DCV, ACV & Current ranges.

2.1 Current Measurements

1.

Set the Range switch to the highest 400A range.

2.

Press the trigger to open transformer jaws, clamp onto one
conductor only and release trigger. Jaws should be completely
closed. Read the current directly on the display. It is
recommended that  the conductor be placed at th e center of
the closed jaws for maximum accuracy (Fig. - 1).

1.  SPECIFICATIONS

1.1 General Specification
Display

n

3

½

 digit liquid crystal display (LCD) with a

maximum reading of 2000 counts.

Polarity

n

Automatic, positive implied, negative polarity
indication.

Overrange

n

(OL) or  (-OL)  is displayed.

Zero

n

Automatic.

Low battery

n

“       ” is displayed when the battery

indication

voltage drops below the operating level.

Measurement

n

3 times per second, nominal.

rate
Operating

n

0°C to 50°C at < 70% relative humidity.

Environment
Storage

n

-20°C to 60°C, 0 to 80% R.H. with battery

Temperature

removed from meter.

Accuracy

n

Stated accuracy at 27

0

C ± 5

0

C,

<75% relative humidity.

Power

n

Two 1.5V  ‘AAA’  Size Battery

Battery life

n

200 hours typical

Dimensions

n

185 x 65 x 28mm (approx.)

Weight

n

170gms  including battery (approx.)

Accessories

n

Pair of test leads x 1, Instruction manual x 1,
1.5V batterys (installed) x 2,
Carring Case x 1, (K type thermocouple upto
260

0

C  for 27T-AUTO only) x 1

Maximum Jaw

n

25mm

Opening

2

1.2 Electrical Specification

Accuracies are ± (% r number of digits) at 27 ± 5°C and
humidity of less than 75% RH.

AC CURRENT (Auto Ranging) 50-60Hz

DC VOLTAGE (Auto Ranging)

Range

Accuracy

Overload Protection

600V

±(0.8% rdg + 3 dgt)

600V DC / AC rms

Range

Accuracy

Overload Protection

600V

±(1.2% rdg + 3 dgt)

600V DC / AC rms

RESISTANCE (Auto Ranging)

Range

Accuracy

Overload Protection

20M

V

V

V

V

V

±(1.2% rdg + 3 dgt)

250V DC / AC rms

AC VOLTAGE (Auto Ranging) 50-60Hz

Continuity Check

Threshold Level

: 40

V

 Approx.

Response Time

: 1m Sec. Approx.

Open Circuit Voltage : 0.4V Approx.
Indication

: ‘   ’ is displayed on LCD and buzzer sounds

at continuity.

Diode Test

Measurement Current : 1.0 ± 0.6 mA Approx.
Open Circuit Voltage

: 1.6V Approx.

3

Range

Accuracy

Overload Protection

2A

±(3% rdg + 5 dgt)

20A

 ±(2% rdg + 3 dgt)

400A AC Max.

200A

±(2% rdg + 5 dgt)

for 1 minute

400A