Digital Input module
or Counter
5.3 Ethernet Communications
Ethernet connection is available through the RJ45 socket located on the side of the DTS Meter.
Modbus TCP, BACnet/IP, SNMP, and DNP3 are available protocols
depending on model ordered
.
Modbus TCP comes along side any other protocol ordered.
Default IP address of the DTS 310 meter is
192.168.1.150
.
Default Modbus Address, BACnet Device ID, and DNP3 address is 100
.
IP address can be configured through the
DTS Toolbox
utility. DTS Toolbox can be downloaded at
http://www.measurlogic.com/software
.
5.4 kWh Pulse Output (Model Dependent)
The DTS 310 comes with a Digital I/O port that can be configured for pulse
outputs.
The DTS 310 will pulse at 1kWh by default but can be changed using DTS Config
or by setting the DIP switches found on the side of the meter.
The relay closure of each pulse will last for 100ms (pulse width) with a minimum
delay of 100ms between any two pulses.
The maximum switching voltage is 50Vdc.
Digital I/O pins 1 and 2 are not used for kWh Pulse.
5.5 Configuring DIP Switches – Communication and Pulse Output Settings
DTS 310 meters fitted with Modbus RTU or BACnet MS/TP communications or Pulse
Outputs come with configurable dip switches on the side of the DTS meter next to the
communications port and can be black or red.
Check the model of the DTS 310 to determine what the DIP switches will do.
The switches are used to manually configure:
Modbus Address
BACnet ID
Baud Rate
CT Primary
Pulse Output
ATTENTION
DIP switches should be set with the power completely removed from the
DTS 310. DIP switch settings will overwrite any settings done through
software until the DIP switches are turned OFF.