Measurlogic DTS 307 Скачать руководство пользователя страница 3

 

 
©Measurlogic

 

Page 3

 

MQ0052-20C 

 

7334 S. Alton Way, Centennial CO 80112 

Tel: 877-777-6567 Tel: 303-805-5252 Fax: 425-799-4780 

e-mail[email protected] 

web: www.measurlogic.com

 

 

 

1

 

PRODUCT OVERVIEW 

 

The One Revenue Grade Meter for all Applications.

 

 
Our DTS 307 or DTS 307/1 energy sub-meter is one of the most versatile meters available on the market.  

 
The standard DTS 307 is a full 3-Phase measurement RGM. If only a single phase 2-Wire system needs to be 
measured, the single channel DTS 307/1 is also available.  

 
The DTS 307 can operate in any environment, requires no external power source to operate, and works with all 

UL or ETL listed 333mV current transformers.  
 
For ease of installation, the DTS 307 is designed to be ultra-compact and fit into most DIN-rail systems. 

 
Some of the exciting features provided with the DTS 307 are  

 

 

Easy to attach pluggable terminals 

 

Modbus RTU or BACnet MS/TP depending on model 

 

Auto-topology Phase Detection 

 

Automatic correction of reversed field mounted CTs 

 

For remote configurability, your DTS 307 comes with our freely downloadable 

DTS Config

 software tool 

 
The DTS 307 is certified to ANSI C12.20 Class 0.5 Revenue Grade.  

 
Also, if in the future, you decide to integrate renewable energy sources, the DTS 307 will conveniently operate as 

a Bi-Directional 

NET

 meter. Easily integrates with Building Automation Systems and Energy Monitoring Software.  

 
Designed and Manufactured in the USA and complies with the Buy American Provisions of ARRA Section 1605.  

 
 

Thank you for choosing Measurlogic and a meter from the DTS Family.

 

 
 

 
 

 

 

NOTE 

Both the DTS 307 and DTS 307/1 variations will be  

generic

ally referred to as the “DTS

 

307” in this document, 

 

except where it is important to distinguish between the two models. 

 

 

Содержание DTS 307

Страница 1: ...Q0052 20C 7334 S Alton Way Centennial CO 80112 Tel 877 777 6567 Tel 303 805 5252 Fax 425 799 4780 e mail info measurlogic com web www measurlogic com DTS 307 DIN Rail Mounted Ultra Compact Revenue Grade Electrical Sub meter ...

Страница 2: ...IRONMENT 6 2 2 SAFETY GUIDELINES 6 2 3 PRODUCT DIMENSIONS 7 2 4 MOUNTING REQUIREMENTS AND GUIDELINES 7 3 CONNECTING TO THE DTS 307 9 3 1 WIRING VOLTAGE AND CURRENT INPUTS 9 3 1 1 Wiring Examples 9 3 2 CONNECTING MULTIPLE LOADS 11 3 3 AUXILIARY POWER 12 4 DTS 307 COMMUNICATIONS INTERFACE 13 4 1 RS 485 2 WIRE COMMUNICATIONS 13 4 2 KWH PULSE OUTPUT MODEL DEPENDENT 14 5 LED DEFINITIONS 14 5 1 STATUS L...

Страница 3: ... Some of the exciting features provided with the DTS 307 are Easy to attach pluggable terminals Modbus RTU or BACnet MS TP depending on model Auto topology Phase Detection Automatic correction of reversed field mounted CTs For remote configurability your DTS 307 comes with our freely downloadable DTS Config software tool The DTS 307 is certified to ANSI C12 20 Class 0 5 Revenue Grade Also if in th...

Страница 4: ...shipping Verify that the following item s match with the corresponding model from the data sheet Installation Guide DTS 307 power energy meter 10 Pin green pluggable screw terminal connector for Voltage and Aux Power Digital Output 6 Pin green pluggable screw terminal connector for Current inputs 3 Pin green pluggable screw terminal connector for Remote RS 485 Communications 1 2 Document Conventio...

Страница 5: ... or connecting too high a voltage can result in death or personal injury and may permanently damage the DTS meter The model number for the normal three phase DTS 307 is DTS 307 Ax xx x F For applications where only single channel measurements are needed the model number is DTS 307 1 Ax xx x F 1 3 1 Current Inputs Current Inputs Value Description Notes A 3 333mV CT Any 333mV CT is acceptable 9 Rope...

Страница 6: ...ent Transformers that are listed to UL 2808 for use in 250Vac or 600Vac line to line circuits as appropriate for the installation may be used with this meter ONLY USE CURRENT TRANSFORMERS WITH OUTPUTS THAT ARE COMPATIBLE WITH THE MODEL OF DTS 307 SEE SECTION 1 3 1 THE USE OF ANY OTHER CURRENT TRANSFORMER CAN RESULT IN PERMANENT DAMAGE TO THE DTS 307 Avoid any electrostatic discharge prior to worki...

Страница 7: ... and or its current transformers Mount the DTS 307 as close as possible to the electrical panel being monitored Make sure that there is at least 4 of clearance above and below the DTS 307 for wiring and connector clearance and of clearance on both sides for cooling Position the DTS 307 such that the labeling can be read from the upright position Only UL or ETL rated conduits and glands should be u...

Страница 8: ...s of the DTS 307 and panel being monitored Recommended Littelfuse BLS002 or equivalent 14 to 12 AWG wire should be used for the voltage and ground with 300V or 600V insulation depending on installation type and according to the table below A UL or ETL certified 600V circuit breaker or equipment switch must be installed as a disconnecting device for the DTS 307 and must be positioned within easy re...

Страница 9: ...Inputs 3 1 1 Wiring Examples ATTENTION Examine the model number of each of your meters to ensure that they are suitable for the type and voltage of the service you are connecting to See section Error Reference source not found for details Note CTs should be connected to the same panel as the voltage connections A N B C A N B C Load DTS 307 3 Phase with Optional Neutral Model Dependent Load A B C D...

Страница 10: ...gic Page 10 MQ0052 20C 7334 S Alton Way Centennial CO 80112 Tel 877 777 6567 Tel 303 805 5252 Fax 425 799 4780 e mail info measurlogic com web www measurlogic com L1 L2 Load DTS 307 1 Single Phase 2 Wire ONLY L1 ...

Страница 11: ... All CT sensors must be of the same manufacturer model number and current rating A full set of CT sensors must be used for each load The pair of wires from the CT sensor to the green pluggable screw terminal must be twisted All CT sensors must be terminated at the green pluggable screw terminal A maximum of 3 loads can be monitored at once Contact Measurlogic if more than 3 loads must be monitored...

Страница 12: ...al 24Vac dc auxiliary power supply to operate A separate IEC 60950 compliant isolated 24Vac dc power supply MUST be used to power these meters Connect the external IEC 60950 compliant isolated power supply to the two 24Vac dc terminals on the DTS 307 meter as shown on the meter label and in the diagram below For clarity the meter voltage terminal and the CT sensors connections are not shown on the...

Страница 13: ... RS 485 is a Daisy Chained Bus terminated at both ends with 120 Ohms DO NOT use a STAR or RING configuration Use 18 22 AWG 2 core shielded twisted pair cable When fitted with Modbus RTU unless otherwise specified through correspondence prior to ordering the default Modbus RTU communications parameters are as follows o Modbus Address 100 Baud Rate 9600 Parity None Data Bits 8 Stop Bits 1 9600 N 8 1...

Страница 14: ...US and REMOTE 5 1 Status LED The STATUS LED consists of a repetition of two flashes and shows whether the measured power is being consumed imported or generated exported as well as the magnitude of the total current The First Flash is the heartbeat and indicates that the meter is ON and the direction of energy The Color and Length of the Second Flash indicates the total current level for all the m...

Страница 15: ...l can be sent to info measurlogic com to request the latest version of DTS Config Unzip the DTSConfigSetup file and double click the setup exe file to begin the installation process Follow the instructions on the screen 7 MAINTENANCE AND SERVICE WARNING There are NO other user serviceable parts in the DTS 307 and no regular maintenance is required If additional maintenance is needed please contact...