CB-7080 & CB-7080D Counter/Timer User's Guide
General syntax format
2-3
Command
Response
Description
Reference
$AA1L
!AA(data)
Read the low trigger level
Page 2-15
$AA1L(data)
!AA
Set the low trigger level
Page 2-16
$AA3N
!AA(data)
Read the max. counter value
Page 2-18
$AA3N(data)
!AA
Set the max. counter value
Page 2-19
$AA4
!AAS
Read the filter status
Page 2-20
$AA4S
!AA
Set the filter status
Page 2-21
$AA5N
!AAS
Read the counter status
Page 2-22
$AA5NS
!AA
Set the counter status
Page 2-23
$AA6N
!AA
Reset the counter
Page 2-24
$AA7N
!AAS
Read the overflow status
Page 2-25
$AAA
!AAG
Read the gate control mode
Page 2-29
$AAAG
!AA
Set the gate control mode
Page 2-30
$AAB
!AAS
Read the input mode
Page 2-31
$AABS
!AA
Set the input mode
Page 2-32
@AADI
!AAS0D00
Read the D/O and alarm state
Page 2-36
@AADO0D
!AA
Set the D/O value
Page 2-38
@AAGN
!AA(data)
Read the preset value
Page 2-44
@AAPN(data)
!AA
Set the preset value
Page 2-45
Alarm mode 0 commands
Table 2-4. Alarm-mode 0 Command Set
Command
Response
Description
Reference
@AAEAN
!AA
Enable the alarm
Page 2-39
@AADAN
!AA
Disable the alarm
Page 2-43
@AAPA(data)
!AA
Set the counter 0 alarm value
Page 2-46
@AASA(data)
!AA
Set the counter 1 alarm value
Page 2-48
@AARP
!AA
Read the counter 0 alarm value
Page 2-50
@AARA
!AA
Read the counter 0 alarm value
Page 2-52
Alarm mode 1 commands
Table 2-5. Alarm-mode 1 Command Set
Command
Response
Description
Reference
@AAEAT
!AA
Enable the alarm
Page 2-40
@AACA
!AA
Clear the latch alarm
Page 2-41
@AADA
!AA
Disable the alarm
Page 2-42
@AAPA(data)
!AA
Set the Hi-alarm value
Page 2-46
@AASA(data)
!AA
Set the Hi-Hi-alarm value
Page 2-48
@AARP
!AA
Read the Hi-alarm value
Page 2-51
@AARA
!AA
Read the Hi-Hi-alarm value
Page 2-53
LED commands
Table 2-6. LED Command Set
Command
Response
Description
Reference
$AA8
!AAS
Read LED configuration
Page 2-26
$AA8V
!AA
Set LED configuration
Page 2-27
$AA9(data)
!AA
Send data to LED
Page 2-28