Installation Manual

 

 

3

1

2

4

L1

L2

L3

N

PE

AC/L2

AC/L1

FG

AC

DC

 

9

The  unit  is  capable  of  being  connected  between  any  2  phases  on  a  3-phase-4-wire  Wye  (Star)  connected 

system. 

 
 
 
 
 
 
 
 
 

10

The unit is capable of dual phase operation, but that requires de-rating output current by at least 20%. 

11

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

 
 
 
For rail fastening

 

1   Tilt the unit slightly rearwards. 

2   Fit the unit over top hat rail. 

3   Slide it downward until it hits the stop. 

4   Press against the bottom for locking. 

5   Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 
 
 
 

12

For other information about the products, please refer to www.meanwell.com for details. 

 

 

Warning / Caution !! 

1

Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do 

not remove the case of the power supply by yourself! 

2

Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides 

together is not allowed. 

3

Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 

4

Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids. 

5

The maximum operating temperature is 50°C for the power supply, please do not install the unit in places with 

high ambient temperature or near fire source. 

6

Instructions for installation in a Pollution Degree 2 environment (Note.1).

 

7

Please do not install the unit in places with high moisture or near the water. 

8

The FG (

     

) must be connected to PE (Protective Earth). 

"Click" 

Содержание TDR-960 Series

Страница 1: ...ontal or table top mounting is not allowed 3 Use copper wire only and recommended wires are shown as below AWG 18 16 14 12 10 Rated Current of Equipment Amp 6A 6 10A 13 16A 16 25A 25 32A Cross section of Lead mm2 0 75 1 00 1 5 2 5 4 Note Current each wire carries should be de rated to 80 of the current suggested above when using 5 or more wires connected to the unit Make sure that all strands of e...

Страница 2: ...se refer to www meanwell com for details Warning Caution 1 Risk of electrical shock and energy hazard All failure should be examined by a qualified technician Please do not remove the case of the power supply by yourself 2 Risk of electric arcs and electric shock danger to life Connecting both the primary and the secondary sides together is not allowed 3 Risk of burn hazard Do not touch the unit i...

Страница 3: ...ion Degree 2 applies where there is only non conductive pollution that might temporarily become conductive due to occasional condensation Generally refer to dry well ventilated locations such as control cabinets Manufacturer MEAN WELL ENTERPRISES Co LTD No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 24891 Taiwan Tel 886 2 2299 6100 Web www meanwell com Branch Office China MEAN WELL GUANGZHOU ENTERP...

Страница 4: ...roducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hexavalent chromium Cr6 Polybrominated biphenyls PBB Polybrominated diphenyl ethers PBDE PCB and its components X O X O O O Metal structure parts X O O O O O Plastic structure parts O O O O O O Accessor...

Отзывы: