Installation Manual
Type
:
TDR DIN rail with Three Phase or High Input Range
(
Series
:
TDR-960
)
TDR-960-24 INPUT: 380 -500VAC 2A 50/60Hz OUTPUT: 24V 40A
TDR-960-48 INPUT: 380 -500VAC 2A 50/60Hz OUTPUT: 48V 20A
Introduction
TDR series is the next generation of Mean Well DIN rail power supplies with three-phase or high input range, this
three-phase DIN unit not only has a slim design of 110mm in width but also possesses a high efficiency of up to
94.5%. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
(
2
)
The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
(
3
)
Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
10
Rated Current of
Equipment (Amp)
6A
6-10A
13-16A
16-25A
25-32A
Cross-section of
Lead(mm
2
)
0.75
1.00
1.5
2.5
4
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
(
4
)
Use wires that can withstand temperatures of at least 80°C such as UL1007.
(
5
)
Recommended wire strapping length is 5mm (0.197”).
(
6
)
Recommended screwdriver is
4mm, slotted type.
(
7
)
The recommended torque setting for terminals is shown as below.
Model
I/P
O/P
TDR-960
10 kgf-cm (9 Lb-in)
8 kgf-cm (7 Lb-in)
(
8
)
Suggested fuse and maximum number of the unit that can be connected to a circuit breaker at 400V are shown
as below.
Model
Fuse
Circuit breaker
C16
D16
TDR-960
T6.3A/H500V
2
4