Installation Manual
3
1
2
4
Rated Current of
Equipment (Amp)
6A
6-10A 13-16A 16-25A 25-32A
Cross-section of
Lead(mm
2
)
0.75 1.00 1.5 2.5 4
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
(
4
)
Use input side wires that can withstand temperatures of at least
90
85
°C such as UL1007.
Use output side wires that can withstand temperatures of at least 100°C such as UL1007.
(
5
)
Recommended wire strapping length is 5mm (0.197”).
(
6
)
Recommended screwdriver is
4mm, slotted type.
(
7
)
The recommended torque setting for terminals is shown as below.
Model I/P
O/P
TDR-240 Switchlab/MB910-952
10 kgf-cm (9 Lb-in)
Switchlab/MB910-635M
10 kgf-cm (9 Lb-in)
(
8
)
Suggested fuse and maximum number of the unit that can be connected to a circuit breaker at 480V are shown
as below.
For USA, CANADA:
Considered current rating of protective device as part of the building installation (A) is 20 A.
For EU:
Model Fuse
Circuit breaker
C16 D16
TDR-240
T5AH/250V
2 4
(
9
)
Mounting Instruction
:
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible.
Admissible DIN rail
:
TS35/7.5 or TS35/15
For rail fastening
:
○
1 Tilt the unit slightly rearwards.
○
2 Fit the unit over top hat rail.
○
3 Slide it downward until it hits the stop.
○
4 Press against the bottom for locking.
○
5 Shake the unit slightly to check the locking action.