Installation Manual
Type
:
TDR DIN rail with Three Phase or High Input Range
(
Series
:
TDR-240
)
Models
Rated Input
Rated Output
DC OK Relay contact
TDR-240-24
380-480 Vac,
3W+PE, Wye system (220-277 Vac /
Phase voltage),
0.69 A, 50/60Hz
24Vdc(24-28Vdc), 10A
(max 240W)
Contact Rating (max.)
30VDC/1A, 30VAC/0.5A
Resistive load.
TDR-240-48
48Vdc(48-55Vdc), 5A
(max 240W)
Note.1:
Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become
conductive due to occasional condensation. Generally refer to
dry, well-ventilated locations, such as
control cabinets.
Note.2: Over voltage Category(OVC) III, according to EN61558-1, , EN61558-2-16, UL61010-1, UL61010-2-201.
Over voltage Category(OVC) II, according to EN62368-1, EN60664-1. Altitude 2000m.
Note.3: RATED INPUT VOLTAGE shall be fluctuated up to +10% and -10%.
Note.4: Others
Introduction
TDR series is the next generation of Mean Well DIN rail power supplies with three-phase or high input range, this
three-phase DIN unit not only has a slim design of 110mm in width but also possesses a high efficiency of up to
94.5%. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. This are open type
device shall be installed in inside of appropriate enclosure or machinery.
Installation
(
1
)
Always allow good ventilation clearances, 20mm below, around the unit in use to prevent it from overheating.
Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
(
2
)
The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
加上正確的安裝方式圖面
(
3
)
Use copper wire only, and recommended wires are shown as below.
AWG
18 16 14 12 10