8
(C)Installation Requirements:
The ISI-501 unit should be mounted on a flat surface or holding rack with suitable
o v e r h e a t e d a n d c a u s e d a n g e r. P l e a s e r e f e r t o t a b l e 7 . 1 o r c o n s u l t w i t h o u r
distributors or us if you have any questions.
strength. In order to ensure the lifespan of the unit, please refrain the unit from
operating in dusty or moist environments. This is a power unit with a built-in DC
fan. Please make sure the ventilation openings are not blocked ; please do not
drive the inverter continuously under heavy load in high ambient environment
because it may prevent the inverter from functioning properly and the inverter's
lifespan may be affected. It is highly recommended that there should be no
objects impeding airflow within 15cm of the ventilation openings.
(B)Suggested Battery Type and Capacity
Note :
If the desired battery type is not Lead-Acid based, please contact the battery
manufacturer for an advised value.
Cross section of wire lead(mm )
2
1.5
2.5
4
6
AWG
14
12
10
8
Suggested Model
48V battery models
24V battery models
12V battery models
PV module input wire
Table 7-1 Suggestion for wire selection
Battery Type
Battery Capacity
Lead-acid
12V / 120Ah ~
24V / 60Ah ~
48V / 30Ah ~
12V / 400Ah
24V / 200Ah
48V / 100Ah
12V models
24V models
48V models
Figure 7.1: Example of Installation
>15cm
Inverter
Air
>15cm
Air
Содержание ISI-501 Series