background image

                           

Installation Manual

 

 

3

1

2

4

 

8

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

For rail fastening

 

 

a

Tilt the unit slightly rearwards. 

b

Fit the unit over top hat rail. 

c

Slide it downward until it hits the stop. 

d

Press against the bottom for locking. 

e

Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 

 
 

 

9

For other information about the products, please refer to www.meanwell.com for details. 

 
ICL-L

: 

1

Before any installation or maintenance work, please disconnect your system from the utility.   

Ensure that it can’t be re-connected inadvertently! 

2

Ventilation holes must be kept free from any obstructions. Also a 10-15 cm clearance must be kept when the 

adjacent device is a heat source. 

3

The recommended torque setting for terminals is shown as below. 

Model 

I/P 

O/P 

ICL-16L 

5.7 kgf‐cm (5 Lb‐in) 

5.7 kgf‐cm (5 Lb‐in) 

ICL-28L 

5.7 kgf‐cm (5 Lb‐in) 

5.7 kgf‐cm (5 Lb‐in) 

4

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

10 

Rated Current of Equipment 

(Amp) 

10 

15 

25 

32 

Cross-section of Lead(mm

2

 ) 

0.8 

1.3 

2.1 

2.5 

Note

Current each wire carries should be de-rated to 80% of the current suggested above 

when using 4-6 wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure 
each contact is connected to wires to prevent too much current stress on a single contact. 

5

For other information about the products, please refer to www.meanwell.com for details. 

 
 
 
 
 
 

"Click" 

Содержание ICL-16L Series

Страница 1: ...ertical the input terminals at the bottom and output on the top Mounting orientations other than that such as upside down horizontal or table top mounting is not allowed 3 Use copper wire only and rec...

Страница 2: ...arance must be kept when the adjacent device is a heat source 3 The recommended torque setting for terminals is shown as below Model I P O P ICL 16L 5 7 kgf cm 5 Lb in 5 7 kgf cm 5 Lb in ICL 28L 5 7 k...

Страница 3: ...ed from foreign objects or dripping liquids 5 Only install the unit in a pollution degree 2 environment Note 1 6 Please do not install the unit in places with high moisture or near the water 7 The max...

Страница 4: ...resent the decisive factor because the inrush current limiters can handle capacitive loads as high as 2500uF 6000uF The input capacity of the power supplies is largely determined by primary side stora...

Страница 5: ...Installation Manual For other model you can use the same method to calculate it...

Страница 6: ...ZHOU ENTERPRISES Co LTD 2F A Building Yuean lndustry Park Huangcun Dongpu Yown Tianhe District Gungzhou China Post Code 510660 Tel 86 20 2887 1200 Web www meanwell com cn U S A MEAN WELL USA INC 44030...

Страница 7: ...oducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hex...

Страница 8: ...to China s Standardization Administration Releases VOC Standards Standard No Name of the Standard GB 30981 2020 Limit of harmful substances of industrial protective coatings GB 33372 2020 Limits for v...

Страница 9: ...eby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6 h CAS No Substance Name 1163 19 5 Decabromodiphenyl ether DecaBDE 68937 41 7...

Отзывы: