background image

                           

Installation

 

Manual

 

 

3

1

2

4

 

8

Suggested

 

fuse

 

and

 

maximum

 

number

 

of

 

the

 

PSUs

 

that

 

can

 

be

 

connected

 

to

 

a

 

circuit

 

breaker

 

at

 

230V

 

are

 

shown

 

as

 

below.

 

Model

 

Fuse

 

Circuit

 

breaker

 

C16

 

D16

 

DRH

120

 

T4A/H250V

 

14

 

16

 

DRT

240

 

F3A/L250V

 

8

 

10

 

DRT

480

 

F6.3A/L250V

 

3

 

5

 

DRT

960

 

F6.3A/L250V

 

2

 

4

 

When

 

an

 

external

 

circuit

 

breaker

 

is

 

utilised,

 

a

 

minimum

 

value

 

is

 

required

 

to

 

avoid

 

undesired

 

tripping

 

of

 

the

 

circuit

 

breaker.

 

9

For

 

DRH

120

 

series,

 

it

 

is

 

capable

 

of

 

being

 

connected

 

between

 

any

 

2

 

phases

 

on

 

a

 

3

phase

4

wire

 

Wye

 

(Star)

 

connected

 

system.

 

 
 
 
 
 
 
 
 
 

Using

 

a

 

fuse

 

or

 

a

 

circuit

 

break

 

to

 

protect

 

the

 

AC/L2

 

input

 

is

 

suggested.

 

The

 

AC/L2

 

input

 

is

 

internally

 

non

protected.

 

10

For

 

DRT

240,

 

DRT

480,

 

and

 

DRT

960

 

series,

 

they

 

are

 

capable

 

of

 

dual

 

phase

 

operation

 

(connecting

 

L1,

 

L3,

 

FG

 

for

 

DRT

960),

 

but

 

that

 

requires

 

de

rating

 

output

 

current

 

by

 

20%.

 

11

Mounting

 

Instruction

 

Mount

 

as

 

shown

 

in

 

figure

 

only,

 

with

 

input

 

terminals

 

down,

 

or

 

else

 

sufficient

 

cooling

 

will

 

not

 

be

 

possible.

 

Admissible

 

DIN

 

rail

TS35/7.5

 

or

 

TS35/15

 

For

 

rail

 

fastening

 

 

a

Tilt

 

the

 

unit

 

slightly

 

rearwards.

 

b

Fit

 

the

 

unit

 

over

 

top

 

hat

 

rail.

 

c

Slide

 

it

 

downward

 

until

 

it

 

hits

 

the

 

stop.

 

d

Press

 

against

 

the

 

bottom

 

for

 

locking.

 

e

Shake

 

the

 

unit

 

slightly

 

to

 

check

 

the

 

locking

 

action.

 

 
 
 
 
 
 
 
 
 
 

12

Electrical

 

Tubing

 

and

 

sleeve

 

 

Recognized

 

Component

 

 

Tubing

 

(YDPU2)

 

and/or

 

sleeving

 

(UZFT2),

 

rated

 

300V,

 

105

 

minimum.

 

13

For

 

other

 

information

 

about

 

the

 

products,

 

please

 

refer

 

to

 

www.meanwell.com

 

for

 

details.

 

 

"Click" 