Installation Manual
3
1
2
4
(
8
)
Suggested fuse is shown as below.
Model Fuse
DDR-120A T10A/L250V
x2
DDR-120B T8A/L250V
x2
DDR-120C T8A/L250V
x1
DDR-120D
T4A/L250V x1
DDR-240B
T10A/L250V x2
DDR-240C
T6.3A/L250V x2
DDR-240D
T6.3A/L250V x1
(
9
)
Mounting Instruction
:
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible.
Admissible DIN rail
:
TS35/7.5 or TS35/15
For rail fastening
:
(
a
)
Tilt the unit slightly rearwards.
(
b
)
Fit the unit over top hat rail.
(
c
)
Slide it downward until it hits the stop.
(
d
)
Press against the bottom for locking.
(
e
)
Shake the unit slightly to check the locking action.
(
10
)
For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution !!
(
1
)
Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do
not remove the case of the power supply by yourself!
(
2
)
Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides
together is not allowed.
(
3
)
Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
(
4
)
Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
(
5
)
Only install the unit in a pollution degree 2 environment (Note.1).
(
6
)
Please do not install the unit in places with high moisture or near the water.
(
7
)
The maximum operating temperature is 55°C for DDR-120 series, please do not install the unit in places with
high ambient temperature or near fire source.
(
8
)
The FG (
) must be connected to PE (Protective Earth).
(
9
)
Output current and output wattage must not exceed the rated value on its specification.
(
10
)
Disconnect system from supply voltage:
Before commencing any installation, maintenance or modification work: Disconnect your system from
supply voltage. Make sure that inadvertent connection in circuit will be impossible!
"Click"