PMBus command
Adjustable range
Tolerance
Default
Model
◎
Control parameter
Figure
8-4
11
OPERATION
CURVE_CV
(Note. 3)
CURVE_FV
(Note. 3)
IOUT_OC_FAULT_LIMIT
CURVE_CC
VOUT_COMMAND
(Note. 2)
VOUT_TRIM
(Note. 2)
00h(OFF) / 80h(ON)
18 ~ 30V
18 ~ VBST
22 ~ 110A
36 ~ 60V
36 ~ VBST
11 ~ 55A
-6 ~ 6V
-12 ~ 12V
N/A
N/A
N/A
80h(ON)
±
0.36V
±
0.36V
±
5.32A
±
0.48V
±
0.48V
±
2.68A
28.8V
27.6V
110A
57.6V
55.2V
55A
±
0.36V
±
0.48V
0V
0V
ALL
24V
24V
24V
24V
24V
24V
24V
48V
48V
48V
48V
48V
48V
48V
CURVE_TC
CURVE_CC_TIMEOUT
CURVE_CV_TIMEOUT
CURVE_FLOAT_TIMEOUT
5.5A ~ 33A
60 ~ 64800 Minute
3A ~ 16.5A
±
5.32A
±
5 Minute
±
2.68A
11A
600 Minute
5.5A
24V
ALL
48V
Minimum readable current
Model
24V
5.3A 1A
±
48V
2.7A 1A
±
1.
will display ZERO amp when output current is less than values in the table below:
READ_IOUT
Note:
Adjustable voltage range
Model
24V
18 ~ 30V
48V
36 ~ 60V
2.
When using PMBus to adjust output voltage, VOUT_COMMAND only can be used to display the
rated voltage of the unit and cannot be written. It is VOUT_TRIM that sets up the amount of
trimmed voltage. Taking DBU-3200-24 as an example, to get a 18V output, please set value of
VOUT_TRIM to -6V. Adjustable voltage range for each model is shown as below:
The value of CURVE_FV should be set less or equal to CURVE_CV,If CURVE_FV is greater than
CURVE_CV, it will be saved as CURVE_FV = CURVE_CV in EEPROM.
Figure
8-5
Figure
8-6
3.