Indoor Unit Central Control Monitor System
MHVAC-DTSM-2010-03
Control System
286
2. Indoor Unit Central Control Monitor System
2.1 CCM03
Indoor CCM, max. 64 indoor units control. Single or all units query and control, such as ON/OFF/Mode
setting/Temp. setting/Fan setting/Mode lock function, Blue background light, LCD display screen.
2.1.1 Basic conditions o f operating the electric controller:
(1)
Applicable range of supply voltage:
Input voltage: Single-phase 198V ~ 242V;
AC input power supply frequency: 50Hz/60Hz compatible.
(2)
Operating environment temperature of electric controller: -15°C~+43°C.
Operating environment RH of electric controller: RH40%~RH90%.
2.1.2 Function categories o f electric controller
Functions of the electric controller:
(1)
System composition
(2)
Keywords and general function description
(3)
Description of electric control functions of centralized controller
(4)
Technical indices and requirements
2.1.3 Function description of each part
System composition:
1.
The centralized controller is used to perform centralized control and data query for the network air
conditioner. Each centralized controller can communicate with a maximum of 64 air conditioners to make
up an air conditioner LAN, and implement centralized monitoring for the air conditioners in the network.
2.
The centralized controller can be interfaced with computer or gateway to implement centralized control
and status query for all air conditioners in the network. It can be connected with WAN via computer or
gateway to implement remote computerized control (with support of computer software). Each local
computer or gateway can be connected to 16 centralized controllers as a maximum.
3.
The master/slave answer mode is implemented for communication between the centralized controller and
the air conditioner, between the computer and the centralized controller. In the LAN composed of
centralized controller and air conditioner, the centralized controller is a master, and the air conditioner is a
slave. In the LAN composed of computer and centralized controller, the computer or gateway is a master,
and the centralized controller is a slave.
Содержание MDVi-D100Q4/N1-C
Страница 11: ...Dimensions MHVAC DTSM 2010 03 Compact Four Way Cassette Type 10 3 Dimensions...
Страница 12: ...MHVAC DTSM 2010 03 Service Space Compact Four Way Cassette Type 11 4 Service Space...
Страница 15: ...Wiring Diagram MHVAC DTSM 2010 03 Compact Four Way Cassette Type 14 MDVi D45Q4 BN1...
Страница 16: ...MHVAC DTSM 2010 03 Wiring Diagram Compact Four Way Cassette Type 15 MDVi D56Q4 BN1...
Страница 63: ...Wiring Diagrams MHVAC DTSM 2010 03 Low Static Pressure Duct Type 62 6 Wiring Diagrams...
Страница 106: ...MHVAC DTSM 2010 03 Service Space New Middle Static Pressure Duct Type A5 105 4 Service Space...
Страница 107: ...Wiring Diagrams MHVAC DTSM 2010 03 New Middle Static Pressure Duct Type A5 106 5 Wiring Diagrams...
Страница 108: ...MHVAC DTSM 2010 03 Wiring Diagrams New Middle Static Pressure Duct Type A5 107...
Страница 109: ...Air Velocity MHVAC DTSM 2010 03 New Middle Static Pressure Duct Type A5 108 6 Air Velocity Airflowvelocity...
Страница 110: ...MHVAC DTSM 2010 03 Air Velocity New Middle Static Pressure Duct Type A5 109...
Страница 126: ...MHVAC DTSM 2010 03 Accessories New Middle Static Pressure Duct Type A5 125 11 Accessories...
Страница 133: ...Service Space MHVAC DTSM 2010 03 Ceiling Floor Type 132 4 Service Space 600mm 600mm...
Страница 204: ...MHVAC DTSM 2010 03 Wiring Diagram Exposed Concealed Floor standing Type 213 7 Wiring Diagram...
Страница 215: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 224 11 2 MDVi D36Z N1 F1 MDVi D45Z N1 F1...
Страница 217: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 226 11 3 MDVi D56Z N1 F1 MDVi D71Z N1 F1...
Страница 219: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 228 11 4 MDVi D80Z N1 F1...
Страница 221: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 230 11 5 MDVi D22Z N1 F2 MDVi D28Z N1 F2...
Страница 223: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 232 11 6 MDVi D36Z N1 F2 MDVi D45Z N1 F2...
Страница 225: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 234 11 7 MDVi D56Z N1 F2 MDVi D71Z N1 F2...
Страница 227: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 236 11 8 MDVi D80Z N1 F2...
Страница 229: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 238 11 9 MDVi D22Z N1 F3 MDVi D28Z N1 F3...
Страница 231: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 240 11 10 MDVi D36Z N1 F3 MDVi D45Z N1 F3...
Страница 233: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 242 11 11 MDVi D56Z N1 F3 MDVi D71Z N1 F3...
Страница 235: ...Exploded View MHVAC DTSM 2010 03 Exposed Concealed Floor standing Type 244 11 12 MDVi D80Z N1 F3...
Страница 241: ...Dimension MHVAC DTSM 2010 03 High Static Pressure Duct Type 250 3 Dimension...
Страница 244: ...MHVAC DTSM 2010 03 Wiring Diagram High Static Pressure Duct Type 253 6 Wiring Diagram...
Страница 258: ...MHVAC DTSM 2010 03 Service Space Console Type 267 4 Service Space...
Страница 287: ...Indoor Unit Central Control Monitor System MHVAC DTSM 2010 03 Control System 296 Dimension...