Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
39
39
RTSM combined status (DPT 22.107)
This is a combined status according to DPT 22.107. The assignment is as follows:
Bit
Beschreibung / Description
Codierung / Encoding
0
Effektiver Wert des Fensterstatus
Effective value of the window status
0 = alle Fenster geschlossen/
all windows closed
1 = mindestens ein Fenster geöffnet/
at least one window opened
1
Effektiver Wert des Präsenzstatus
Effective value of the presence status
0 = keine Meldung einer Präsenz/
no occupancy from presence detectors
1 = mindestens ein Melder belegt/
occupancy at least from one presence
detector
3
Status der Komfortverlängerung
Status of comfort prolongation User
0 = Komfortverlängerung nicht aktiv/
comfort prolongation User not active
1 = Komfortverlängerung aktiv/
comfort prolongation User not active
Table 36: Assignment
–
RTSM combined status DPT 22.107
4.4.2.4 Operating mode after reset
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Operating mode after
reset
▪
Comfort with configured setpoint
▪
Standby with configured setpoint
▪
Hold previous state and setpoint
Setting which operating mode or
behaviour is to be activated after
a bus voltage return.
Operating mode after
reprogramming
▪
Comfort
▪
Standby
Setting the operating mode after
reprogramming.
Only with the setting "Hold
previous state and setpoint".
Table 37: Settings
–
Operating mode after reset
•
Comfort with configured setpoint
After a bus voltage return, the comfort is activated with the setpoint that was specified by
the ETS.
•
Standby
with configured setpoint
After a bus voltage return, the Standby mode is activated with the setpoint that was
specified by the ETS (Comfort setpoint minus Standby reduction).
•
Hold previous state and setpoint
The temperature controller recalls the setpoint and mode that was set before the bus was
switched off. With this selection, the parameter "
Operating mode after reprogramming
"
can be used to additionally set which operating mode is active after reprogramming.