Technical Manual Temperature Controller
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
23
4.4.2 Operating modes & Setpoints
The following settings are available at the ETS-Software:
Figure 8: Operating modes & setpoints
The chart shows the dynamic range of the operating modes and setpoints:
ETS-text
Dynamic range
[default value]
comment
Basis comfort setpoint
18,0°C
–
25,0°C
[21,0°C]
The basis comfort setpoint is the reference
point of the control.
Night reduction
Lowering in K
0 K
–
10,0 K
[3,0 K]
Lowering of the temperature by choosing
the operating mode night.
Relative to the basis comfort setpoint.
Standby reduction
Lowering in K
0 K
–
10,0 K
[2,0 K]
gets activated when no other operating
mode was chosen
The lowering is relative to the basis
comfort setpoint.
Setpoint frost protection
3°C
–
12°C
[7°C]
Setpoint of the operating mode frost
protection.
indicated by an absolute value
Setpoint heat protection
24°C
–
40°C
[35°C]
Setpoint of the operating mode heat
protection.
indicated by an absolute value
Table 12: Operating modes & setpoints