Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
84
84
4.7 Temperature measurement
Function only available for Glass Push Button II Smart/Push Button Smart 86 with temperature
sensor
The following figure shows the menu for temperature measurement:
Figure 56: Settings – Temperature measurement
The table below shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Temperature
measurement
not active
active
Activation of temperature
measurement
External temperature
value
not active (internal 100%)
external 10% (internal 90%)
external 20% (internal 80%)
…
external 90% (internal 10%)
Activation of an extension for
temperature measurement
Send measurement value
cyclic
not active
1 min – 4 h
[20 min]
Activation of the cyclic sending
for the temperature
measurement value
Send measurement value
at change
nicht senden
0,1 °C – 5 °C
[0,2 °C]
Activates the sending of the
current temperature value from
a certain change
Adjustment value for
internal temperature
-50 … 50 x0,1K
[0]
Increase / decrease the internal
temperature to correct the
measured temperature
Temperature for upper
message value
not active
20°C – 45°C
Activation of a message when a
certain temperature is reached
Temperature for lower
message value
not active
3°C – 30°C
Activation of a message if the
temperature falls below a certain
temperature
Table 78: Settings – Temperature measurement