Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
25
25
4.2.3.2 Status values 1-3
The following figure shows the settings for activating the Status values 1-3:
Figure 13: Settings – State Values 1 - 3
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
State values 1 - 3
Not active
On/Off (DPT 1.001)
Percent 0…100% (DPT 5.001)
Value 0…255 (DPT 5.005)
Current (mA) (DPT 7.012)
Brightness (Lux) (DPT 7.013)
Temperature (°C) (DPT 9.001)
Brightness (Lux) (DPT 9.004)
Wind speed (m/s) (DPT 9.005)
Humidity (%) (DPT 9.007)
Air quality (ppm) (DPT 9.008)
Current (mA) (DPT 9.021)
Setting the DPT to be
displayed as status value
Text for unit
any text
[up to 5 bytes allowed]
Enter the text describing the
unit
Description for
measurement
any text
[up to 15 bytes allowed]
Enter the text describing the
measurement
Table 12: Settings – State Values 1 - 3
The following table shows the available communication objects for the information screen:
Number
Name
Length
Usage
120
State text 1
14 Byte
Receiving a status text
121
State text 2
14 Byte
Receiving a status text
122
State value 1
Receiving a status value.
DPT according to parameter setting
123
State value 2
Receiving a status value.
DPT according to parameter setting
124
State value 3
Receiving a status value.
DPT according to parameter setting
Table 13: Communication objects – State Values/State texts