
B
B
A
A
B
B
E
E
19
3-INSTALLATION AND ASSEMBLY
If the wall that is to be drilled through is made of flammable material, the
INSTALLER MUST
adequately insulate the pipe of the stove that
passes through it, using suitable insulating material (1.3 - 5 cm thick with min. thermal conductivity 0.07 W/m°K).
However, the pipe inserted in the wall must be adequately insulated in order not to disperse heat and soundproof the released air.
It is advisable to set up the ducts of similar length to distribute the air evenly, otherwise it will go through the
shorter channel or that with less windings.
In the example in figure 6 and 7 (front and rear view), the air ducting is of equal length for a total of 8 metres, i.e. the pipes
(B)
will be
approximately 4 metres each. If the pipes are of different length, the total must always add up to 8 metres (e.g. 3 + 5 metres). In this case,
the heat will not diffuse into the rooms uniformly.
The air recirculation in the room occurs through the perforated plate on the rear side of the stove.
The air volume that you wish to exit from the upper and rear parts of the stove can be set separately by adjusting the ventilation power
directly with the remote control.
REMOVING THE AIR DIFFUSER
Diffuser E must be removed from the back panel of the stove if you wish to channel the air. Remove the two upper screws and extract
diffuser E from the grooves.
FIGURE 6 - FRONT VIEW OF THE SYSTEM AIR OUTLET
FIGURE 7 - REAR VIEW OF THE SYSTEM AIR OUTLET
SCREW
GROOVES
Technical Dept. - All rights reserved - Reproduction is prohibited