CHILLED WATER FAN COILS MF – McQuay FCF PM05D_ENG
page 7/36
TECHNICAL DATA
2 PIPES
3 ROWS
MODELS
012C
020C
025C
035C
050C
060C
080C
090C
Nominal Air Flow
(High/Medium/Low)
m
3
/h
290/245/
197
380/296/
210
497/349/
260
705/565/
400
853/695/
465
1141/969/
705
1360/
1063/82
4
1500
/1368/
1190
Available Static Pressure
Pa
--
--
--
--
--
--
--
--
Total Cooling Capacity
1
kW
1.3
1.8
2.7
3.6
4.8
5.9
6.9
8.0
Total Sensible Capacity
1
kW
1.0
1.5
1.9
2.6
3.6
4.6
5.3
5.8
Heating Capacity
2
kW
2.2
2.7
3.6
4.8
6.2
8.1
10.5
12.0
Water Flow Rate
l/s
0.063
0.085
0.129
0.170
0.227
0.282
0.358
0.347
Water Pressure Drop - Cooling
kPa
4
5
10
16
28
33
18
20
Lp (Sound Pressure Level)
3
dB(A)
38/35/33
42/37/32
42/35/32
48/44/39
47/39/31
53/48/41
51/47/41
53/51/47
Power Supply
V/ph/Hz
220~240/1/50
Fan N°.
n°
1
1
2
2
2
2
3
3
Max Power Supply
4
kW
0.024
0.044
0.044
0.059
0.068
0.102
0.147
0.167
Cond. Drain Connections
mm
20
20
20
20
20
20
20
20
Water Connections
inches
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
Total volume
litres
0.792
1.158
1.525
1.89
Weight [with package]
kg
20 [22]
24 [27]
26 [30]
35 [39]
Weight with cabinet
[with package]
kg
22 [25]
29 [32]
32 [37]
45 [50]
Dimens. unit (WxHxD)
mm
704x540x224
904x540x224
1104x540x224
1304x540x224
Dimens. with cabinet (WxHxD)
mm
910x539x230
1110x539x230
1310x539x230
1510x539x230
2 PIPES
4 ROWS
MODELS
412C
420C
425C
435C
450C
460C
480C
490C
Nominal Air Flow
(High/Medium/Low)
m
3
/h
254/215/
176
369/321/
240
445/330/
250
677/545/
380
811/663/
456
1068/915/
672
1300/
1165/
908
1450/
1288/
1120
Available Static Pressure
Pa
--
--
--
--
--
--
--
--
Total Cooling Capacity
1
kW
1.5
2.7
3.1
4.6
5.3
6.4
7.1
8.3
Total Sensible Capacity
1
kW
1.1
1.7
2.1
2.8
3.7
5.0
5.5
5.8
Heating Capacity
2
kW
2.3
2.8
4.2
5.3
6.8
8.4
11.0
12.5
Water Flow Rate
l/s
0.073
0.098
0.149
0.193
0.251
0.304
0.397
0.409
Water Pressure Drop - Cooling
kPa
4
5
10
14
21
20
18
17
Lp (Sound Pressure Level)
3
dB(A)
38/36/33
42/37/32
41/34/32
47/43/38
47/39/31
53/48/41
51/47/41
53/50/47
Power Supply
V/ph/Hz
220~240/1/50
Fan N°.
n°
1
1
2
2
2
2
3
3
Max Power Supply
4
kW
0.021
0.050
0.051
0.056
0.077
0.107
0.143
0.167
Cond. Drain Connections
mm
20
20
20
20
20
20
20
20
Water Connections
inches
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
Total volume
litres
1.056
1.545
2.033
2.52
Weight [with package]
kg
24 [26]
28 [30]
30 [33]
35 [39]
Weight with cabinet
[with package]
kg
26 [27]
31 [35]
35 [40]
45 [50]
Dimens. unit (WxHxD)
mm
704x540x224
904x540x224
1104x540x224
1304x540x224
Dimens. with cabinet (WxHxD)
mm
910x539x230
1110x539x230
1310x539x230
1510x539x230
NOTES
1 At the following nominal conditions: nominal air flow; 7/12°C inlet/outlet water temperature; 27°C db/19°C wb inlet air temperature; High speed
2 At the following nominal conditions: nominal air flow 50°C inlet water temperature; 20°C inlet air temperature; same water flow as for cooling; High speed
3 At High/Medium/Low speed; nominal air flow; measured in a room of 100m volume and 0.5 sec. reverberation time ( e.g. office/conference room with carpet on the floor)
4 Nominal Air Flow; High Fan Speed