Special Precautions When
Dealing With R410A Unit
R410A is a new HFC refrigerant which does not damage
the ozone layer. The working pressure of this new
refrigerant is 1.6 times higher than conventional
refrigerant (R22), thus proper installation/servicing is
essential.
•
Never use refrigerant other than R410A in an air-
conditioner which designed to operate with R410A.
•
POE oil is used as lubricant for R410A compressor,
which is different from the mineral oil used for R22
compressor. During installation or servicing, extra
precaution must be taken not to expose the R410A
system too long to moist air. Residual POE oil in the
piping and components can absorb moisture from the
air.
•
To prevent mischarging, the diameter of the service
port on the flare valve is different from that of R22.
•
Use tools and materials exclusively for refrigerant
R410A. Tools exclusively for R410A are manifold valve,
charging hose, pressure gauge, gas leak detector, flare
tools, torque wrench, vacuum pump and refrigerant
cylinder.
•
As an R410A air conditioner incurs higher pressure
than R22 units, it is essential to choose the copper
pipes correctly. Never use copper pipes thinner than
0.8mm even though they are available in the market.
•
If the refrigerant gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the
refrigerant gas comes into contact with fire, a
poisonous gas may occur.
•
When installing or removing an air conditioner, do not
allow air or moisture to remain in the refrigerant cycle.
Unit Indicator Lights
IR Signal Receiver
When an infrared remote control operating signal is
transmitted, the signal receiver on the indoor unit beeps to
confirm acceptance of the signal transmission.
Figure 21. Indicator Lights Location – Indoor Unit
Cooling Only Unit
Table 6
shows the LED indicator lights for the cooling only
unit under normal operation and fault conditions. The LED
indicator lights are located at the bottom right side of the
indoor unit. (
See Figure 21 and Figure 22).
Figure 22. LED Indicator Lights for Cooling Only Unit
Table 6. LED Indicator Lights: Normal Operation and Fault
Conditions for Cooling Only Unit
Power
Sleep
Timer
Dry
Mode
or
Fault
Action
Timer -
Sleep -
Dry -
Once
every 2
sec.
Room
air
sensor
contact
loose/short
Repair
or
replace
Twice
every 2
sec.
Indoor
coil
sensor
contact
loose/short
Repair
or
replace
3 times
every 2
sec.
Sensor
coil
problem,
compressor
overload
protection
trip or gas
leak.
Check
circuit
breaker,
check
for gas
leak
CAUTION
!
•
R410A must be charged as liquid. Usually R410A
cylinder is equipped with a dip-pipe for liquid
withdrawal. If there is no dip-pipe, the cylinder
should be inverted so as to withdraw liquid R410A
from the valve.
•
Do not top-up when servicing leak, as this will
reduce the unit performance. Vacuum the unit
thoroughly and then charge the unit with fresh
R410A according to the amount recommended in
the specification.
•
Do not touch the compressor or refrigerant piping
when the chiller is running. If necessary wear
protective gloves.
ON
/
ON or OFF
Blinking
Page 20
IM-5WMF(SEER13)-0706
Содержание M5LC10C
Страница 6: ...Model M5LC20C 20CR 25C 25CR Outdoor Unit Page 6 IM 5WMF SEER13 0706...
Страница 15: ...INDOOR UNIT MODEL M5WM 25F Page 15 IM 5WMF SEER13 0706 OUTDOOR UNIT MODEL M5LC 25C...
Страница 16: ...INDOOR UNIT MODEL M5WM 10FR 15FR OUTDOOR UNIT MODEL M5LC 10CR 15CR IM 5WMF SEER13 0706 Page 16...
Страница 17: ...INDOOR UNIT MODEL M5WM 20FR IM 5WMF SEER13 0706 Page 17 OUTDOOR UNIT MODEL M5LC 20CR...
Страница 18: ...INDOOR UNIT MODEL M5WM 25FR IM 5WMF SEER13 0706 Page 18 OUTDOOR UNIT MODEL M5LC 25CR...