112
Special Precautions For R407c
Special Precautions When Dealing With Refrigerant R407C Unit
1) What Is New Refrigerant R407C?
R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus conformed
to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's lubricant. Its refrigerant
capacity and performance are about the same as the refrigerant R22.
2) Components
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) Characteristic
•
R407C liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence,
when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change
and subsequently affect the system performance.
DO NOT
add new refrigerant to leaked system. It is
recommended that the system should be evacuated thoroughly before recharging with R407C.
•
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid phase.
Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to make
certain that only original composition of R407C is being charged into the system.
•
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22 compressor.
Extra precaution must be taken not to expose the R407C system too long to moist air.
4) Check List Before Installation/Servicing
•
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to temporarily cover
the ends of the tubing prior to installation
•
Compressor oil
No additional charge of compressor oil is permitted.
•
Refrigerant
No other refrigerant other that R407C
•
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) Handling And Installation Guidelines
Like R22 system, the handling and installation of R407C system are closely similar. All precautionary measures; such as
ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and
vacuuming are equally important requirements. However, due to zeotropic nature of R407C and its hydroscopic POE oil,
additional precautions must be taken to ensure optimum and trouble-free system operation.
a)
Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a
heat-pump system, install a two-way flow filter dryer along the liquid line.
b)
During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.
Содержание M4MC075D
Страница 71: ...70 Blower Performance Curves BLOWER PERFORMANCE CURVE MDB 075D...
Страница 72: ...71 BLOWER PERFORMANCE CURVE MDB 100D...
Страница 73: ...72 BLOWER PERFORMANCE CURVE MDB 125D...
Страница 74: ...73 BLOWER PERFORMANCE CURVE MDB 150D...
Страница 75: ...74 BLOWER PERFORMANCE CURVE MDB 200D...
Страница 76: ...75 BLOWER PERFORMANCE CURVE MDB 250D L s 70 65 60...
Страница 77: ...76 BLOWER PERFORMANCE CURVE MDB 300D...
Страница 78: ...77 BLOWER PERFORMANCE CURVE MDB 400D...
Страница 79: ...78 BLOWER PERFORMANCE CURVE MDB 500D...
Страница 80: ...79 BLOWER PERFORMANCE CURVE MDB 075D DR VERY HIGH STATIC...
Страница 81: ...80 BLOWER PERFORMANCE CURVE MDB 100D DR VERY HIGH STATIC...
Страница 82: ...81 BLOWER PERFORMANCE CURVE MDB 125D DR VERY HIGH STATIC...
Страница 83: ...82 BLOWER PERFORMANCE CURVE MDB 150D DR VERY HIGH STATIC...
Страница 89: ...88 MODEL MDB 500D4 DR4 NOTE 1 WITH SEQUENTIAL CONTROLLER 2 VERTICAL AIR DISCHARGE...
Страница 90: ...89 Outlines And Dimensions Outdoor MODEL MMC 075 100D DR MODEL MDB 125D DR...
Страница 91: ...90 MODEL MMC 150D DR OUTDOOR UNIT WITH BALL VALVE MODEL MMC 075D...
Страница 92: ...91 MODEL MMC 100D MODEL MMC 125D...
Страница 93: ...92 MODEL MMC 150D...
Страница 97: ...96 MODEL MDB 400D4 vs MMC 100D x 4 MDB 500D4 vs MMC 125D x 4 WITH SEQUENTIAL CONTROLLER...
Страница 99: ...98 MODEL MDB 125DR vs MMC 125DR WITH U1 125 SLM3 HANDSET MODEL MDB 150DR vs MMC 150DR WITH U1 125 SLM3 HANDSET...
Страница 101: ...100 MODEL MDB 400DR4 vs MMC 100DR x 4 MDB 500DR4 vs MMC 125DR x 4 WITH SEQUENTIAL CONTROLLER...
Страница 102: ...101 Refrigerant Circuit Diagram MODEL MMC 075D 100D 125D 150D...
Страница 103: ...102 MODEL MLC 061C...
Страница 104: ...103 MODEL MMC 075DR 100DR 125DR 150DR R22 M4MC 75DR 100DR 125DR 150DR R407C...
Страница 177: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...