10

IM 743-1

Replacing an Existing Modbus Communication Module

To replace a Modbus Communication Module:

1.

 

Remove power from the MicroTech II Chiller Unit Controller.

2.

 

Locate the Serial Card slot on the MicroTech II Chiller Unit Controller (see Figure 3.)

3.

 

Pull the network cable connector from the Modbus Communication Module.

4.

 

Remove the cover from the Serial Card slot. Use a small screwdriver to pry it off from one end.

5.

 

Grasp the Modbus Communication Module and carefully pull it from the controller.

6.

 

Install the new Modbus Communication Module.

7.

 

Figure 4 shows the Serial Card slot that details how the 8-pin plug mates to the 8-pin header on
the Modbus Communication Module.

8.

 

Grasp the Modbus Communication Module, with the network connector on the underside.  The 8-
pin header on the Modbus Communication Module must mate to the 8-pin plug in the unit
controller. The plug has a guide on each end to direct the Modbus Communication Module into
the mating guide on the header.

Note:  

Since it is impossible top see the connectors mate, this operation relies more on feeling
the Modbus Communication Module into the connector than seeing the connectors
mate.

9.

 

Insert the Modbus Communication Module, pointing up, into the slot, rolling it into a level
position as you move it into the slot.

10.

 

Keeping the Modbus Communication Module 

level

, move it into the slot until you feel the

connectors line up.  The correct position seems to be level, toward the left side of the slot, and
down slightly from the top.

11.

 

When you feel the connectors align, press the Modbus Communication Module into the
connector.  Verify that it is firmly seated in the connector.

12.

 

Replace the cover on the Serial Card slot.  Slip the cover over the network connector plug.

13.

 

Insert the network cable connector into the Modbus Communication Module.

Unit Setup for Network Control

To Setup the MicroTech II Unit Controller for network control:

1.

 

Disable the chiller. The chiller should not be operating while performing this setup.

2.

 

At the MicroTech II Chiller Unit Controller keypad,
a.

 

In the SET UNIT SPs (1) screen, set the setpoint “Source” equal to “Local”. Use the
Operator Password of “100”.

b.

 

In the SET UNIT SPs (1) screen, set the “Enable” setting equal to “Off”.

c.

 

In the SET UNIT SPs (13) screen, set the protocol parameters. Use the Manager Password
of “2001”.

Note: 

Password screens listed are for Centrifugal Chillers.  Passwords/screens for other models
may be different.

3.

 

Verify with the chiller technician that the chiller is operational.

4.

 

At the MicroTech II Chiller Unit Controller keypad, in the SET UNIT SPs (1) screen, set the
setpoint “Source” equal to “BAS”. Use the Operator Password of “100”.

Note: 

See the appropriate Operation Manual for specific instructions for changing variables with
the keypad/display.

Содержание IM 743

Страница 1: ...Cooled Global Scroll ACZ Air Cooled Scroll Condensing Unit WGZ Water Cooled Global Scroll AGS Air Cooled Global Screw WGS Water Cooled Global Screw NOTICE Use this manual to physically install the com...

Страница 2: ...to the Network 11 Network Topology 11 Addressing and Establishing Communications 11 Network Address and Baud Rate 11 Configuring the Unit Controller 11 Service Information 13 Test Procedures 13 Repla...

Страница 3: ...ir Cooled Scroll Chiller Installation Operation and Maintenance Manual www mcquay com IOMM WGZ McQuay International MicroTech II Water Cooled Scroll Chiller Installation Manual www mcquay com IOMM WPV...

Страница 4: ...hange any information contained herein without prior notice The user is responsible for determining whether this software is appropriate for his or her application The following are trademarks or regi...

Страница 5: ...ules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment Operation of this equipment in a residential are...

Страница 6: ...jor Components RS 485 Network Connetor 8 Pin Header Modbus Connector RS 485 Network Connector This connector connects the Modbus Communication Module to the RS 485 network Pin Function 1 Reference 2 I...

Страница 7: ...rom the Serial Card slot if it hasn t already been removed Use a small screwdriver to pry the cover off from one end 4 Remove the plastic knockout in the cover 5 Figure 4 shows the Serial Card slot th...

Страница 8: ...e of the network cable to Pin 2 of the connector plug b Connect the other wire to Pin 3 of the connector plug c No wire is connected to the remaining pin Figure 3 Serial Card Slot Location on Unit Con...

Страница 9: ...IM 743 1 9 Figure 5 Network Cable Routing and Connections Figure 6 Network Connection Detail Net w ork Cab le Pin 3 Pin 2...

Страница 10: ...the slot 10 Keeping the Modbus Communication Module level move it into the slot until you feel the connectors line up The correct position seems to be level toward the left side of the slot and down s...

Страница 11: ...a MicroTech II Chiller Unit Controller is set in the unit controller keypad display The Modbus network address and data transmission rate Baud Rate is only available in the keypad display when the pr...

Страница 12: ...d via the network or with the keypad display The appropriate Operation Manual provides default values and keypad operation The MicroTech II Chiller Modbus Protocol Information Document ED 15063 provid...

Страница 13: ...ll does not respond contact the McQuay Controls Customer Support group at 866 4MCQUAY 866 462 7829 Replaceable Parts List Network Connection Plug Generic Replacement Parts If you lose this terminal bl...

Отзывы: