Installation and Maintenance Manual

IM 702-3

Group

Controls

Part Number: IM 702-3

Date

November 2004

Supersedes: IM 702-2

© 2004 McQuay International

MicroTech II

TM

Applied 

 

Rooftop Unit Controller and

Self-Contained Unit Controller
LonWorks® Communication Module

<

Space Comfort Controller (SCC) Module

<

Discharge Air Controller (DAC) Module

NOTICE

Use this manual to physically install the communications module into the unit and connect the unit to your
network. You also need the appropriate McQuay Engineering Data Sheet known as the Protocol Data Packet to
integrate the unit into your network. The Protocol Data Packet contains addressing details, BACnet® and
LonWorks® protocol information, and a list of the data points available to the network. See the Reference
Documents section of this document for part numbers of Protocol Data Packets. These documents are available
from your local McQuay International representative and for downloading at the McQuay International web site:

www.mcquay.com

.

Содержание IM 702-3

Страница 1: ...s module into the unit and connect the unit to your network You also need the appropriate McQuay Engineering Data Sheet known as the Protocol Data Packet to integrate the unit into your network The Pr...

Страница 2: ...7 Integration 12 Network Connection 12 Network Topology 12 Free Topology Networks 12 Free Topology Restrictions 13 Doubly Terminated Networks 13 Doubly Terminated Topology Restrictions 14 Addressing a...

Страница 3: ...MicroTech II Vertical Self Contained Unit Controller Installation Manual OM711 McQuay International MicroTech II Vertical Self Contained Discharge Air Controller Operation Manual OM712 McQuay Internat...

Страница 4: ...protection against harmful interference when the equipment is operated in a commercial environment Operation of this equipment in a residential area is likely to cause harmful interference in which c...

Страница 5: ...ce Documents for part numbers Figure 2 Building Automation System MicroTech II Main Control Board MicroTech II LonWorks Communications Module MicroTech II Keypad LonWorks Interface Adapter LonWorks Wo...

Страница 6: ...Standard Network Variable Types SNVTs and Standard Network Configuration Parameters SCPTs in accordance with the LonMark profiles used on the LonWorks network into the variables and parameters used in...

Страница 7: ...able harness down to the shelf below the controller and to the left along the shelf to the edge Route the cable through a hole down the raceway to Terminal Block TB2 c Connect the cable harness white...

Страница 8: ...10 Connect the MicroTech II LonWorks Communications Module to the network a Replace the network plug in P8 See Figure 3 11 Reconnect the network to TB 2 terminals 128 and 129 if it is necessary Figure...

Страница 9: ...nection Schematic Diagram 522 523 LonWorks Communications Module Main Control Board MCB Unit Terminal Block Tb2 128 129 LonWorks Network A B Figure 6 Mount LonWorks Communications Module 12 Pin Header...

Страница 10: ...10 IM702 3 Figure 7 Cable Harness Routing Applied Rooftop Unit LonWorks Comunications Module Controller Cable Shelf Cable Raceway Terminal Block TB2 Network Cable Communications...

Страница 11: ...IM702 3 11 Figure 8 Cable Harness Routing Self Contained Unit Controller LonWorks Comunications Module Terminal Block TB2 Network Cable Harness Communications...

Страница 12: ...s Additional nodes may be added with little regard to existing cable routing Free Topology Networks A LonWorks free topology network means that devices nodes can be connected to the network in a varie...

Страница 13: ...ft 450 m 22 AWG 1312 ft 400 m 1640 ft 500 m 16 AWG 1640 ft 500 m 1640 ft 500 m The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node to node distance...

Страница 14: ...ld connect two controllers with one continuous piece of cable in order to reduce the risk of com munications errors If you must splice the cable use crimp type butt connectors good or solder best Do n...

Страница 15: ...ware and configured at the factory for stand alone unit operation The unit is ready to operate in a stand alone manner with default set point parameters that can be changed with the unit s keypad disp...

Страница 16: ...Length parameter should not be set higher than 1024 for BACnet IP or 501 for BACnet MSTP 4 The Xs in Device Object Name are factory set equal to the last nine digits of the 18 digit number on the bar...

Страница 17: ...ce personnel of McQuay International in Minneapolis Minnesota 763 553 5330 A Return Goods tag must be included with the returned material Enter the required information to expedite handling and prompt...

Страница 18: ...2 3 2004 McQuay International www mcquay com 800 432 1342 This document contains the most current product information as of this printing For the most current product information please go to www mcqu...

Отзывы: