1-8
N
L
COMP
A
4WV
OF
N
L
COMP
A
4WV
OF
N
L
The electrical power must be provided with
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3mm.
Interconnection Cable
Terminal
Strip
Indoor
Unit
Terminal Strip
Outdoor Unit
CE 30CR
Indoor unit
CE 30CR
Outdoor unit
SL 30CR
Voltage range (2)
220V – 240V/1Ph/50Hz +
!
or
208V – 230V/1Ph/60Hz +
!
Power Supply Cable size
mm
2
4.0
Number of conductors (1)
3
Interconnection Cable size
mm
2
4.0
Number of conductors (1)
7
Recommended fuse (1)
A
25
The electrical power must be provided with
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3mm.
Interconnection Cable
Terminal
Strip
Indoor
Unit
Terminal Strip
Outdoor Unit
N
L
COMP
A
4WV
OF
N
L
COMP
A
4WV
OF
CE 30CR
Indoor unit
CE 40CR
CE 50CR
CE 61/62CR
Outdoor unit
SL 40CR
SL 50CR
SL 60CR/61CR
Voltage range (2)
380V – 415V/3Ph/50Hz + N +
!
or 208V – 230V/3Ph/60Hz + N +
!
Power Supply Cable size
mm
2
(50/60Hz)
1.5/2.5
2.5/4.0
2.5/4.0
Number of conductors (1)
5
5
5
Interconnection Cable size
mm
2
(50/60Hz)
1.5/1.5
1.5/1.5
1.5/1.5
Number of conductors (1)
7
7
7
Recommended fuse (1)
A (50/60Hz)
10/20
16/25
16/25
Power Supply
Cable
Power Supply
Cable
Outdoor Coil Sensor
Outdoor Coil Sensor
IMPORTANT:
(1) These values are for information only, they should be checked and selected to comply with the local and/
or national codes and regulations. They are also subjected to the type of installation and size of conductors
used.
(2) The appropriate voltage range should be checked with label data on the unit. ETL listed unit is only
applicable to 60Hz power supply only.
!
!