304 C – 02/06 D – pag. 3/16 

Electrical data ALZ/ALP “B” 

Unit size 

011.1  013.1  017.1  020.1  022.2  025.2  029.2 033.2  036.2  038.2 

Standard voltage (1) 

400 V  -  3f –  50 Hz + 

NEUTRAL

 

Nominal unit current (2) 

32,3 

37,8 

45,4 

54,8 

64,1 

75,9 

83,9 

93,5 

99,4  109,8 

Max compressor current (3) 

29,3 

35,4 

44,4 

54,6 

61,0 

74,4 

83,8 

95,2 

98,0  109,6 

Fans current  

5,4 

5,4 

5,4 

5,4 

8,1 

8,1 

8,1 

8,1 

10,8 

10,8 

Max unit current (3) 

34,7 

40,8 

49,8 

60,0 

69,1 

82,5 

91,9  103,3  108,8  120,4 

Max unit inrush current (4) 

151,6  154,3  203,1  207,8  186,2  195,0  246,0  253,2  260,4  268,2 

Max unit current for wires sizing (5) 

45,4 

63,4 

65,4 

75,4 

88,1  124,1  126,1  128,1  140,8  150,8 

Notes: (1)

 Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. 

 (2) 

Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp. 

(3) 

Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp. 

(4) 

Inrush current of biggest comp nominal absorbed current of the other compressors.

 

(5) 

Compressor FLA + fans current.

 

 

 

Operating limits  

Entering evaporator 

water temperature 

Leaving evap. water 

temp.(without glycol) 

Evaporator water 

∆∆

t   Ambient temperature 

ALZ 

Min. (°C) 

Max (°C) 

Min. (°C) 

Max (°C) 

Min. (°C) 

Max (°C)  Min.(°C)(*)  Max (°C) 

011.1 

20 

15 

15 

42 

013.1 

20 

15 

15 

42 

017.1 

20 

15 

14 

42 

020.1 

20 

15 

12 

40 

022.2 

20 

15 

15 

42 

025.2 

20 

15 

13 

40 

029.2 

15 

10 

12 

40 

033.2 

15 

10 

10 

40 

036.2 

20 

15 

15 

42 

038.2 

20 

15 

15 

40 

 

(*)

 for ambient temperature down to –18°C low ambient kit is required (fan speed control) 

 

 

Altitude correction factor 

Elevation above sea level (m) 

300 

600 

900 

1200 

1500 

1800 

Barometric pressure (mbar) 

1013 

977 

942 

908 

875 

843 

812 

Cooling capacity correction factor 

1,000 

0,991 

0,981 

0,972 

0,962 

0,953 

0,943 

 

Ethylene glycol and low ambient temperature correction factors 

Air ambient temperature °C 

-3 

-8 

-15 

-23 

-35 

% of ethylene glycol correction factor 

10 

20 

30 

40 

50 

Cooling capacity correction factor  

0,986 

0,980 

0,973 

0,966 

0,960 

Flow rate correction factor  

1,023 

1,054 

1,092 

1,140 

1,200 

Water pressure drops correction factor 

1,061 

1,114 

1,190 

1,244 

1,310 

 

Low temperature operation performance factors 

Ethylene glycol/water leaving temperature °C 

-2 

-6 

-8 

Cooling capacity correction factor 

0,842 

0,783 

0,725 

0,615 

0,562 

Power input compressors correction factor 

0,950 

0,934 

0,918 

0,870 

0,845 

Min % of ethylene glycol 

10 

20 

20 

30 

30 

Max air ambient temperature °C  

40 

40 

38 

34 

32 

 

Fouling factor 

Fouling factor 

m

°C / kW 

Cooling capacity 
correction factor 

0,044 

1,000 

0,132 

0,986 

0,308 

0,939 

Содержание ALZ "B"

Страница 1: ...ooled motocondensing unit ALZ B 011 1 038 2 ALP B 011 1 038 2 Cooling capacity from 40 to 145 kW 50Hz Refrigerant HFC 407C Scroll Compressors Installation and maintenance manual 304 C 02 06 D Date Jun...

Страница 2: ...Repeated check the safety devices and continous cycling of control components must be analyzed and corrected before being reset The simple design of the refrigeration circuit totally eliminates potent...

Страница 3: ...Min C Max C Min C Max C Min C Max C Min C Max C 011 1 8 20 4 15 4 8 15 42 013 1 8 20 4 15 4 8 15 42 017 1 8 20 4 15 4 8 14 42 020 1 8 20 4 15 4 8 12 40 022 2 8 20 4 15 4 8 15 42 025 2 8 20 4 15 4 8 1...

Страница 4: ...ap heat recovery cond 2 kW 100 4 116 1 123 9 143 9 151 3 Heating capacity 2 kW 132 4 152 4 166 3 189 6 200 9 Power input heat recovery cond 2 kW 35 8 41 5 47 9 51 2 55 4 Desuperheaters heating capacit...

Страница 5: ...placed on the unit base that must to be removed only after the final destination In case the unit has to be moved again a similar solution is necessary Handling and lifting Care should be taken to avo...

Страница 6: ...from the obstacle fig 4 For other installation solutions consult McQuay technicians Acoustic protection The low noise levels of the ALZ units means that they meet most of the most restrictive regulati...

Страница 7: ...of fan speed Full alarm management Can be linked up to serial line for supervisory telemaintenance control Can be linked up to an external terminal unit Controlled devices Compressor Condensation fans...

Страница 8: ...EO high supply voltage OFF OFF OFF OFF OFF OFF EP eeprom boot OFF OFF OFF OFF OFF OFF Cn discon remote terminal Ht high temperature ON Electrical features Power supply Voltage supply range 24V 15 10 5...

Страница 9: ...D7 for alarm connection jumper connector for expansion board connection digital relay outputs to manage any controlled device the Y1 GND analog output for the connection of the optional boards for the...

Страница 10: ...or main board P1 pin strip relative to the Y2 analog output to be normally left open except in particular situations see parameters F3 and F4 User Interface Terminal The terminal allows the access to...

Страница 11: ...alue blinks on display the alarm code appears on the LCD alternatively with the temperature value After the alarms have been cleared either with automatic reset or by pressing the and keys simultaneou...

Страница 12: ...de password which is different from the USER one to prevent any unauthorized access to the data Setting the password 00 flashes on the display Pressing the t and u buttons will allow you to stop the b...

Страница 13: ...isplays values Buzzer sound after 5 password for USER parameters stores parameters in eeprom stores parameters in eeprom silences the buzzer PRG SEL Normal operating condition after 5 password for FAC...

Страница 14: ...a Check the actual unit line voltage to be sure it is the same you can read on the compressor nameplate within 10 and that phase voltage unbalance does not exceed 3 Verify that adeguate power supply a...

Страница 15: ...304 C 02 06 D pag 15 16 ALZ ALP B Unit dimensions Fans Arrangement ALZ ALP B 011 1 020 1 ALZ ALP B 022 2 033 2 ALZ ALP B 036 2 038 2 2780 011 1 020 1 3530 022 2 033 2 4280 036 2 038 2...

Страница 16: ...hanges in design and construction at any time without notice thus the cover picture is not binding McQuay Italia S P A S S Nettunense km 12 300 00040 Cecchina Roma Italia Tel 06 937311 Fax 06 9374014...

Отзывы: