User Manual

 

MCOHome Technology Co., Ltd

 

www.mcohome.com

 

 

4

 

Valve Output Voltage Display 

In the state of power on/off

long press

       

to enter into valve output voltage interface, the valve output voltage 

value will be displayed in the area of temperature. Output range:0~10V.   

 

Parameter Setting

 

 

Power Failure Memory   

        Under  the  shutdown  state,  press&  hold 

       

will  enter  interface  for  power  failure  memory 

Selection, “PAGE” displays. Press

  or 

  to change setting value, then press “M” to confirm and 

return. 

After power failure: 

000 (default) indicates device will be in shutdown state (“OFF”) when power on again; 

        001 indicates device will be in working interface when power on again; 

002 indicates device will stay the status before power failure when power on again. 

 

 

Temp. Calibration/ Temp. Setting Range 

        Under the shutdown state, press & hold

  will enter interface for temperature calibration, 

“-ERR”displays. The calibration range is among -5.0 ~ +5.0 

.

 

        Press 

  or 

  to change setting value, then press “M” save and enter interface for temp. 

Range setting (0~99

):

 

        1. “-HI-” displays, the default value are 35

. Press 

  or 

  can set the value; 

        2. Press “M” again, “-LO-”displays, the default value is 5

. Press

  or 

  can set the value; 

        3. Then press “M” to confirm and return to “OFF”.

 

 

 

Screen Brightness/ Fan continuously work/ Key-touch volume 

        Under the shutdown state, press & hold “M” will enter interface for screen brightness selection 

(LED), Press 

  or 

  can choose: (press “M” to confirm the choice and enter into next setting) 

111 indicates the screen will always be full bright when power on; 

000 (default) indicates without button operation for a long time (15 seconds), the screen  will be 

half bright automatically. 

 

Press “

M

” again will enter interface for Fan continuously work choice: 

000 (default) indicates device will shutdown fan and valve if room temp. Reaches setting temp.; 

001 indicates device will shutdown valve only if room temp. Reaches setting temp. The fan will 

continuously work in low speed. 

Press “M” again will enter interface for Key-touch volume (BEEP) setting: 

    0: Off                      1: On       

 

 

Temp. Sensor Error

   

       

    If temperature sensor does not work, “E1” displays , fan stops and valve closes automatically.

 

 

Z-Wave Operation 

 

Including & Excluding of Z-Wave network 

        Under  the  shutdown  state,  press  &  hold 

  to  enter  interface  for  inclusion  or  exclusion  of       

Z-Wave  network.  Before  device  included  into  network,  “-  -  -”  will  display  on  the  screen.  Then 

press

once, device will enter learning mode to get a node ID. If inclusion is success, a node ID will 

display on the screen in a few seconds. 