5
W N H
MILLIVOLT
BURNER
CIRCUIT
1
2
3
4
NEUTRAL
HOT
120V
UNI-MATCH
WATER FEEDER
WFE-120
SERIES 67
LOW WATER
CUT-OFF
• Install wire from 120 volt circuit
'Neutral'
wire to terminal
'N'
on water feeder.
• Install wire from 120 volt circuit
'Hot'
wire to terminal
'H'
on
water feeder and terminal
'3'
on low water cut-off.
• Install wire from terminal
'W'
on the water feeder
to terminal
'4'
on the low water cut-off.
Diagram 8
WFE-120 / 67 with millivolt burner circuit
W N H
MILLIVOLT
BURNER
CIRCUIT
1
2
3
4
NEUTRAL
HOT
24V
TRANSFORMER
120V
UNI-MATCH
WATER FEEDER
WFE-24
SERIES 67
LOW WATER
CUT-OFF
• Install wire from 120 volt circuit
'Neutral'
wire to
the transformer input
'Neutral'
terminal.
• Install wire from 120 volt circuit
'Hot'
wire to the
transformer input
'Hot'
terminal.
• Install wire from transformer output
'Neutral'
terminal to terminal
'N'
on the water feeder.
• Install wire from transformer output
'Hot'
terminal
to terminal
'H'
on water feeder and terminal
'3'
on
low water cut-off.
• Install wire from terminal
'W'
on the water feeder
to terminal
'4'
on the low water cut-off.
NOTE: Transformer provided by others.
Diagram 9
WFE-24 / 67 with millivolt burner circuit
UNI-MATCH
WATER FEEDER
WFE-24
2
1
P
1
P
2
A
W N H
HYDROLEVEL 400
Factory
Jumper
Bar
• Connect wire from terminal
'N'
of water feeder to terminal
'2'
on LWCO.
• Connect wire from terminal
'H'
of water feeder to terminal
'1'
on LWCO.
• Connect wire from terminal
'W'
of water feeder to terminal
'A'
on LWCO.
Diagram 10
WFE-24 / Hydrolevel 400
UNI-MATCH
WATER FEEDER
WFE-24
2
1
P
1
P
2
A
W N H
HYDROLEVEL CG400
Factory
Jumper
Bar
BURNER
• Connect wire from terminal
'N'
of water feeder
to terminal
'2'
on LWCO.
• Connect wire from terminal
'H'
of water feeder
to terminal
'1'
on LWCO.
• Connect wire from terminal
'W'
of water feeder
to terminal
'A'
on LWCO.
Diagram 11
WFE-24 / Hydrolevel CG400
UNI-MATCH
WATER FEEDER
WFE-120
2
1 P
1
P
2
A
W N H
Factory
Jumper
Bar
HYDROLEVEL 450
• Connect wire from terminal
'N'
of water feeder
to terminal
'2'
on LWCO.
• Connect wire from terminal
'H'
of water feeder
to terminal
'1'
on LWCO.
• Connect wire from terminal
'W'
of water feeder
to terminal
'A'
on LWCO.
Diagram 12
WFE-120 / Hydrolevel 450
UNI-MATCH
WATER FEEDER
WFE-120
2
1
P
1
P
2
A BURNER
W N H
HYDROLEVEL CG450
Factory
Jumper
Bar
• Connect wire from terminal
'N'
of water feeder
to terminal
'2'
on LWCO.
• Connect wire from terminal
'H'
of water feeder
to terminal
'1'
on LWCO.
• Connect wire from terminal
'W'
of water feeder
to terminal
'A'
on LWCO.
Diagram 13
WFE-120 / Hydrolevel CG450