5

W N H

MILLIVOLT

BURNER

CIRCUIT

1

2

3

4

NEUTRAL

HOT

120V

UNI-MATCH
WATER FEEDER
WFE-120

SERIES 67

LOW WATER

CUT-OFF

• Install wire from 120 volt circuit 

'Neutral'

wire to  terminal 

'N'

on water feeder.

• Install wire from 120 volt circuit 

'Hot'

wire to terminal 

'H'

on 

water feeder and terminal 

'3'

on low water cut-off.

• Install wire from terminal 

'W'

on the water feeder 

to terminal 

'4'

on the low water cut-off.

Diagram 8 

WFE-120 / 67 with millivolt burner circuit

W N H

MILLIVOLT

BURNER

CIRCUIT

1

2

3

4

NEUTRAL

HOT

24V

TRANSFORMER

120V

UNI-MATCH
WATER FEEDER
WFE-24

SERIES 67

LOW WATER

CUT-OFF

• Install wire from 120 volt circuit 

'Neutral'

wire to 

the transformer input 

'Neutral'

terminal.

• Install wire from 120 volt circuit 

'Hot'

wire to the 

transformer input 

'Hot'

terminal.

• Install wire from transformer output 

'Neutral'

terminal to terminal 

'N'

on the water feeder.

• Install wire from transformer output 

'Hot'

terminal

to terminal 

'H'

on water feeder and terminal 

'3'

on

low water cut-off.

• Install wire from terminal 

'W'

on the water feeder 

to terminal 

'4'

on the low water cut-off.

NOTE: Transformer provided by others.

Diagram 9 

WFE-24 / 67 with millivolt burner circuit

UNI-MATCH
WATER FEEDER
WFE-24

2

1

P

1

P

2

A

W N H

HYDROLEVEL 400

Factory
Jumper

Bar

• Connect wire from terminal 

'N'

of water feeder to terminal 

'2'

on LWCO.

• Connect wire from terminal 

'H'

of water feeder  to terminal 

'1'

on LWCO.

• Connect wire from terminal 

'W'

of water feeder  to terminal 

'A'

on LWCO.

Diagram 10

WFE-24 / Hydrolevel 400

UNI-MATCH
WATER FEEDER
WFE-24

2

1

P

1

P

2

A

W N H

HYDROLEVEL CG400

Factory
Jumper

Bar

BURNER

• Connect wire from terminal 

'N'

of water feeder 

to terminal 

'2'

on LWCO.

• Connect wire from terminal 

'H'

of water feeder 

to terminal 

'1'

on LWCO.

• Connect wire from terminal 

'W'

of water feeder 

to terminal 

'A'

on LWCO.

Diagram 11 

WFE-24 / Hydrolevel CG400

UNI-MATCH
WATER FEEDER
WFE-120

2

1 P

1

P

2

A

W N H

Factory
Jumper

Bar

HYDROLEVEL 450

• Connect wire from terminal 

'N'

of water feeder 

to terminal 

'2'

on LWCO.

• Connect wire from terminal 

'H'

of water feeder 

to terminal 

'1'

on LWCO.

• Connect wire from terminal 

'W'

of water feeder 

to terminal 

'A'

on LWCO.

Diagram 12 

WFE-120 / Hydrolevel 450

UNI-MATCH
WATER FEEDER
WFE-120

2

1

P

1

P

2

A BURNER 

W N H

HYDROLEVEL CG450

Factory
Jumper

Bar

• Connect wire from terminal 

'N'

of water feeder 

to terminal 

'2'

on LWCO.

• Connect wire from terminal 

'H'

of water feeder 

to terminal 

'1'

on LWCO.

• Connect wire from terminal 

'W'

of water feeder 

to terminal 

'A'

on LWCO.

Diagram 13 

WFE-120 / Hydrolevel CG450