Maintenance

Put mask or protective glass when approach battery, make sure not put battery next to fire/ smoking place. It can

prolong battery life and easy to judge when battery need replacement by proper maintenance. If the maintenance

way differs from this manual, users can only make the maintenance method according to battery usage and

using reliability. All maintenance needs the professionals to execute.

1

Checking

Try to make all checking under float charging conditions. Measurements should be made according to

specification from suppliers and keep the records for future collation.

1

1 Monthly checking

Record for monthly checking

1

1

1 All batteries float charging voltage

1

1

2 Current and voltage from charger

1

1

3 Temperature, ventilation and monitor equipments situation.

1

1

4 Eye check record for battery string:

1) Battery appearance: terminal, connector, any corrosive phenomena with battery rack.

2

The clearance region between batteries and rack

3

Any phenomena of crack or leakage for battery

4

Any phenomena of deformation for battery and rack

1

2 Quarterly checking

Apart from checking clause of above 1.1 as quarterly checking,

1

Resistance per block

2

Temperature of negative terminal for each battery

3

Check connect resistance at random ( at least check 10% or not less than 6 connectors), if resistance is

higher than initial resistance, then need to check all connectors' resistance and dig out reason.

1

3 Yearly checking and initial checking

Apart from checking clause of above 1.1 and 1.2 as yearly checking ,

please also checking following

issues and keep record ( Need to collate with previous records.

1

Check all connector resistance;

2

Try to check AC current and voltage from rectifier.

1

4 Special checking

Batteries need inspection to check if they were get damaged in special situation (like over-discharge,

abuse charging machine or charging machine can not work properly ect). The inspection

includes all

yearly checking clause and make records.

2. Ripple Voltage of rectifier

We recommend ripple Voltage of rectifier should not be bigger than 0.5% of charging voltage, and librating ripple

time should be shorter than 8 millisecond.

3. Battery cleaning

Use water or carbonic acid water to clear battery and cover.

4. Capacity test

If batteries can work properly, no need to check capacity. Only to check capacity when doubt battery capacity.

Battery cut voltage after discharge should not be lower than suppliers specification. Before capacity testing,

make sure battery get fully charged for more than 48 hours under float charge, if not, make a equalization charge

for 24 hours then let batteries rest for 8-24 hours.

. .
. .
. .
. .






12

Common Faults & Solutions

Common Faults & Solutions

1

2

3

4

5

6

7

No.

Common Fault

Solution

Leakage

Pls contact the supplier for replacements.

Crack

Low floating V.

Battery less capacity

High temp.round pole

Abnormal Appearance

Grounding Fault

Abnormal connect & inner
resistance

Pls contact the supplier for replacements.

After 24-48hrs equalization charger, still low,

Inspect connect point, charger, ventilation and
charging current.

Pls contact the supplier for replacements.

Check leakage or ground faulty.

Check good connect or charging method.

After 24-48hrs equalization charger, still low,

8

Содержание FCDG6-200

Страница 1: ...ICAL MANUAL VALVE REGUALATED GEL BATTERY Add Cangjiang Industrial Park Gaoming Foshan 528513 Guangdong China Tel 86 757 88806928 Fax 86 757 88594006 E mail info mca battery com Website www mca battery...

Страница 2: ...T4 16 5 6 Unit mm Terminal T3 20 5 8 Terminal T5 Unit mm TERMINALS C B A E D F Size mm Size inch Weight Model Nominal voltage V Rated capacity Ah L W H Total H L W H Total H kg lb Terminal Layout FCD...

Страница 3: ...e battery when moving it 3 Smoking or lighting fires are strictly forbidden Keep the battery away from electric arc 4 Avoid short circuit The battery electrolyte splashes onto eyes skin or clothes flu...

Страница 4: ...at the positive turns into PbSO and part of Pb at the negative also turns into PbSO In this electro chemical reaction both positive and negative elec trodes generate PbSO In the charging state the le...

Страница 5: ...connecting strip Conduct the test according to the probe potion on the instructionmanual If the data range is 20 bigger than that during installation fix screws again to the torque of 11 3N M If the d...

Страница 6: ...1 2 as yearly checking please also checking following issues and keep record Need to collate with previous records 1 Check all connector resistance 2 Try to check AC current and voltage from rectifier...

Страница 7: ...Table Show the battery parts and special function 11 12 13 BATTERY CONSTRUCTION 14 MATERIAL SAFETY DATA SHEET...

Отзывы: