6 Commissioning
20/28
Product codes 400B19EN01 | 401B19EN01
ENR 300 level controller | ETS 100 and ETS 200 signalling devices
6.4
Activating test mode
1
Set "Test / Func." slider to "Test".
2
To test the function of the relays and LEDs, set the step on the "SENSITIVITY"
rotary switch.
6.4.1 Test mode steps - ENR 300 level controller
Probe rods
Sensor signal
display
Slider position
Active relay
output
(terminals)
Steps 1 and 5 … 16
E1 & E2 are not
wetted
"RELAY 1":
LED off
"Full"
42, 43
"Empty"
41, 43
E2 is not wetted
"RELAY 2":
LED off
"Full"
32, 33
"Empty"
31, 33
Step 2
M, E1 & E2 are
wetted
"RELAY 1":
LED lit
"Full"
41, 43
"Empty"
42, 43
E2 is not wetted
"RELAY 2":
LED off
"Full"
32, 33
"Empty"
31, 33
Step 3
E1 & E2 are not
wetted
"RELAY 1":
LED off
"Full"
42, 43
"Empty"
41, 43
M & E2 are
wetted
"RELAY 2":
LED lit
"Full"
31, 33
"Empty"
32, 33
Step 4
M, E1 & E2 are
wetted
"RELAY 1":
LED lit
"Full"
41, 43
"Empty"
42, 43
M & E2 are
wetted
"RELAY 2":
LED lit
"Full"
31, 33
"Empty"
32, 33