background image

2

Units shown in figures 1 and 2 may be installed in
combustible countertop and must be spaced at least (1

²

from) combustible sides and rear wall above countertop.

Unit shown in figure 3 may be installed in combustible
countertop and adjacent to (0

²

from) combustible sides

and rear wall above countertop.

Dimension A = 30-inches minimum clearance between top
of the cooking surface and the bottom of an unprotected
wood or metal cabinet, or A = 24-inches minimum when
bottom of wood or metal cabinet is protected by not less
than 1/4 inch flame retardant millboard covered with not
less than no. 28 msg sheet steel, .015 inch stainless steel,
.024 inch aluminum or .020 inch copper.

“To eliminate the hazard of reaching over heated surface
units, cabinet storage space located above the surface
units should be avoided. If cabinet storage is to be
provided, the hazard can be reduced by installing a range
hood that projects horizontally a minimum of 5-inches
beyond the bottom of the cabinets.”

CAUTION:

SOME CABINETS

AND BUILDING

MATERIALS ARE NOT DESIGNED TO WITHSTAND
THE HEAT PRODUCED BY THE NORMAL SAFE
OPERATION OF A LISTED APPLIANCE. DIS-
COLORATION OR DAMAGE, SUCH AS DELAMINA-
TION, MAY OCCUR.

COUNTER

TOP

BASE

CABINET

3/8

²

FLEXIBLE CABLE 3

MIN.

FURNISHED AND

INSTALLED BY MANUFACTURER

(CONNECT TO 240/120-VOLT

ELECTRICAL SERVICE.)

30

²

Cooktop with Coil Elements

If cooktop is to be secured to countertop, remove main top and attach burner box to countertop at (4) corners.

To remove main top from burner box, remove all (4) surface units and drip bowls. Remove the (4) mounting
screws from main top. (Tabs on side of element openings.)

CAUTION:

DO NOT REMOVE GREEN GROUND WIRE FROM MAIN TOP. WHEN REPLACING MAIN

TOP, USE CAUTION TO BE SURE WIRES ARE NOT PINCHED UNDER SWITCH SHIELD.

FIGURE 1

“A”

Содержание MEC4430AA

Страница 1: ...separate switch and fuse box UNIT CONNECTIONS This unit is supplied with a 240 208 volt wiring system consisting of 2 insulated conductors and 1 bare grounding wire for use on a 3 wire 120 240 or a 12...

Страница 2: ...units should be avoided If cabinet storage is to be provided the hazard can be reduced by installing a range hood that projects horizontally a minimum of 5 inches beyond the bottom of the cabinets CAU...

Страница 3: ...3 36 Cooktop with Coil Elements FIGURE 2 30 Smoothtop Ceramic Cooktop FIGURE 3 3 8 FLEXIBLE CABLE 48 LONG FURNISHED AND INSTALLED BY MANUFACTURER CONNECT TO 240 120 VOLT ELECTRICAL SERVICE...

Страница 4: ...ONEXIONES DE LA UNIDAD Esta unidad se provee con un sistema de cableado de 240 208 voltios que consiste de 2 conductores aislados y 1 alambre desnudo de conexi n a tierra para usarse en un circuito de...

Страница 5: ...pulgadas cuando la parte inferior del gabinete de metal o madera est protegido por cuando menos 1 4 pulgada de anchoderecubrimientodecart n gruesode combusti nlenta con una hoja de acero de cuando me...

Страница 6: ...BLE DE 1 2 DE 36 DE LARGO PROVISTO E INSTALADO POR EL FABRICANTE CONECTE A UN SERVICIO EL CTRICO DE 240 120 VOLTIOS 3 3 8 DE PROFUNDIDAD 7 8 DERECHO T PICO CONDUCTOR DEL ALAMBRE DE 6 FRENTE DE LA UNID...

Страница 7: ...ue s par CONNEXIONS DE L APPAREIL Cet appareil est fourni avec un c blage 240 208 V qui consiste en2conducteursisol setunfil demassenuetseraccorde un circuit de d rivation trifilaire de 120 240 ou 120...

Страница 8: ...minimum si le bas de l armoireen boisou enm tal estprot g par du carton ignifuge d un minimum de 1 4 pouce d paisseur couvert au minimum de t le d acier n 28 MSG d acier inoxydable de 0 015 pouce d p...

Страница 9: ...D GAGEMENT DE 10 8 CM L INT RIEUR POUR LE CONDUIT ANGLE DROIT ET LE FIL 8 6 CM DE PROFONDUR C BLE FLEXIBLE DE 13 MM DE DIAM TRE ET 91 4 CM DE LONG FOURNI ET POS EN USINE RACCORDER UNE ALIMENTATION LEC...

Отзывы: