SERVICING

24

TROUBLESHOOTING

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

NOTE:

  Discharge body’s static electricity before touching unit. 

An electrostatic can adversely affect electrical components.

Use the following precautions during air handler installation 

and servicing to protect the integrated control module from 

damage. By putting the air handler, the control, and the per-

son at the same electrostatic potential, these steps will help 

avoid exposing the integrated control module to electrostat-

ic discharge. This procedure is applicable to both installed 

and uninstalled (ungrounded) blowers.

1.  Disconnect all power to the blower. Do not touch the 

integrated control module or any wire connected to 

the control prior to discharging your body’s electro-

static charge to ground.

2.  Firmly touch a clean, unpainted, metal surface of the 

air handler blower near the control. Any tools held in a 

person’s hand during grounding will be discharged.

3.  Service integrated control module or connecting 

wiring following the discharge process in step 2. Use 

caution not to recharge your body with static electrici-

ty; (i.e., do not move or shuffle your feet, do not touch 

ungrounded objects, etc.). If you come in contact with 

an ungrounded object, repeat step 2 before touching 

control or wires.

4.  Discharge your body to ground before removing a 

new control from its container. Follow steps 1 through 

3 if installing the control on a blower. Return any old 

or new controls to their containers before touching 

any ungrounded object.

DIAGNOSTIC CHART

WARNING

HIGH VOLTAGE

To avoid personal injury or death due to 

electrical shock, disconnect electrical power 

before performing any service or maintenance. 

Refer to the Troubleshooting Chart at the end of this man-

ual for assistance in determining the source of unit oper-

ational problems. The 7 segment LED display will provide 

any active fault codes. An arrow printed next to the display 

indicates proper orientation (arrow points to top of display).  

See following image.

7 Segment

Diagnostic

Displays

Fault

Recall

FAULT CODE HISTORY

The heat pump’s diagnostics menu provides access to the 

most recent faults. The six most recent faults can be ac-

cessed through the control board seven segment displays 

or the CoolCloud mobile app. Any consecutively repeated 

fault is stored a maximum of three times.

Example: A leak in the system, low refrigerant charge or an 

incompletely open stop valve can cause the unit to flash error 

code E15. This error code suggests that the unit is experi-

encing operation at low pressure. The control will only store 

this fault the first three consecutive times the fault occurs.

NOTE:

 THE FAULT LIST CAN BE CLEARED AFTER 

PERFORMING MAINTENANCE OR SERVICING THE 

SYSTEM TO ASSIST IN THE TROUBLESHOOTING 

PROCESS.

DEVICE STATUS

This menu displays information about the systems current 

status. This menu can be utilized to confirm correct func

-

tionality of the equipment and for troubleshooting purposes.

The following items will be displayed:

•  Heat Capacity Request Percentage

•  Cool Capacity Request Percentage

•  Heat Capacity Request During Defrost Percentage

• 

Dehumidification Request Percentage

•  Reversing Valve Status

• 

Reported Airflow by Indoor Unit

•  Boost Mode

•  Previous Defrost Run Time

SENSOR DATA

The following sensor values will be displayed:

•  Outdoor Temperature

•  Coil Temperature

•  Liquid Line Temperature

•  Discharge Temperature

•  Defrost Sensor

•  Suction Pressure

PUMP DOWN / CHARGE MODE

This function can be enabled in this menu.

SYSTEM VERIFICATION TEST

The mandatory system verification test is enabled from this 

menu, which enables a functional check of the equipment, 

in addition to ensuring proper stop valve position.

Содержание Amana AVZC18

Страница 1: ...is possible however that during its lifetime a product may require service Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the...

Страница 2: ...ith any other combination is not covered by the warranty SAFE REFRIGERANT HANDLING While these items will not cover every conceivable situa tion they should serve as a useful guide WARNING Refrigerant...

Страница 3: ...e a venting terminal may discharge a combination of a hot lubricating oil and refrigerant b flammable mixture if system is contaminated with air in a stream of spray which may be dangerous to anyone i...

Страница 4: ...Bridge Technology A V P E C 25 B 1 4 AA 1 2 3 4 5 6 7 8 9 10 11 12 Brand Engineering A Single Piece Air Handler Major Minor Revisions Not used for inventory management Unit Applica on Refrigerant Char...

Страница 5: ...It continues to soak up heat and vaporizes as it proceeds through the coil cooling the indoor coil down to about 48 F Heat is continually being transferred to the cool fins and tubes of the indoor eva...

Страница 6: ...in the outdoor unit Please note that outdoor equipment operational sound lev els may increase while the equipment is running in BOOST MODE Disabling BOOST MODE will provide the quietest and most effic...

Страница 7: ...ensor values will be displayed Outdoor Temperature Coil Temperature Liquid Line Temperature Discharge Temperature Defrost Sensor Suction Pressure PUMP DOWN CHARGE MODE This function can be enabled in...

Страница 8: ...er Tli Thermistor Tgi Thermistor HP LP ID HP LP Sensor Filter Dryer Access Tube Filter LEGEND Tl Thermistor Outdoor Liquid Temperature Td Thermistor Discharge Temperature Tb Thermistor Defrost Sensor...

Страница 9: ...MOSTAT AND WIRING Communicating Thermostat Wiring The maximum wire length for 18 AWG thermostat wire is 250 feet THERMOSTAT AND WIRING WARNING Line voltage now present With power ON thermostat calling...

Страница 10: ...at which the high pressure control cuts out If it cuts out at 605 PSIG to 17 PSIG it is operating normally See causes for high head pres sure in Service Problem Analysis Guide If it cuts out below thi...

Страница 11: ...one lead to ground 3 Using the other lead of the Megometer check the insula tion between U to ground V to ground W to ground Compressor Terminal Unpainted Refrigerant Piping TESTING COMPRESSOR WINDING...

Страница 12: ...he range of 40 to 50 TESTING REVERSING VALVE CHECKING REVERSING VALVE AND SOLENOID Reversing valve used in heat pumps could potentially leak internally Discharge gases can leak into the suction inside...

Страница 13: ...n a single red LED The estimated CFM is displayed on an on board 7 segment display For example if the CFM is 1240 CFM 7 segment display shows FC A 12 40 The AVPEC air handlers may be used in a fully c...

Страница 14: ...low check thermostat wiring for opens shorts 5 The network troubleshooting chart provides additional communications troubleshooting information Terminals Nonimal dc Voltages 1 to C 2 5 Vdc 2 to C 2 5...

Страница 15: ...E Failure to follow proper procedures may cause property damage personal injury or death IMPORTANT NOTE Because of the potential damage to compressors do not allow suction pressure at service valve to...

Страница 16: ...s may cause property damage personal injury or death CAUTION Use refrigerant certified to AHRI standards Used refrigerant may cause compressor damage and is not covered by the warranty Most portable m...

Страница 17: ...ubcooling equals the degrees of temperature decrease below the saturation temperature at the existing pressure 1 Attach an accurate thermometer or preferably a ther mocouple type temperature tester to...

Страница 18: ...igerant oil and motor insulation to decom pose forming acids and sludge If a compressor is suspected of being burned out attach a refrigerant hose to the liquid line dill valve and properly remove and...

Страница 19: ...igerant lines must not touch wall Strap Sleeve Strap Sleeve Wire Tie Wire Tie PVC Pipe Caulk Outside Wall Armaflex Wrapped Suction Line Liquid Line Wood Block Between Studs IMPORTANT Refrigerant lines...

Страница 20: ...are securely anchored Strapping placed around the suction line only SECTION 3 OUTDOOR UNIT IS ABOVE THE INDOOR UNIT 1 Gas line must be sloped continuously towards the indoor unit 2 The maximum elevati...

Страница 21: ...be installed in a manner to prevent liquid migration to the outdoor unit from the indoor unit The heat pump condenser unit is shipped with a predetermined factory charge level as shown in the followi...

Страница 22: ...inlet of the unit Negative Pressure 2 Measure the static pressure of the supply duct Pos itive Pressure 3 Add the two 2 readings together 4 Consult unit nameplate for quantity of air Checking Static...

Страница 23: ...circulator blower This blower provides several automatically adjusted blower speeds The Specification Sheet applicable to your model provides an airflow table showing the relationship between airflow...

Страница 24: ...is man ual for assistance in determining the source of unit oper ational problems The 7 segment LED display will provide any active fault codes An arrow printed next to the display indicates proper or...

Страница 25: ...GE TRIP OR OVER TEMPERATURE TRIP Voltage or Temperature Trip b7 INCOMPLETE PARAMETER SENT TO MOTOR Incomplete Parameters Sent to Motor b9 LOW INDOOR AIRFLOW Minor Error Code without EH mode No Display...

Страница 26: ...circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten or correct wiring connection Verify con...

Страница 27: ...eTalk communications wiring Coil Temperature Sensor Open No coil temperature Sensor not connected or broken wire Check if coil sensor is connected Replace coil sensor Coil Temperature Sensor Shorted N...

Страница 28: ...ric heat operation during defrost 1 low stage 2 default high stage Heat Pump Indoor Airflow Trim default 0 Heat Pump Heating Airflow Off Delay Time default 60 seconds Cooling Airflow On Delay Time def...

Страница 29: ...at pump for primary heating Menu is enabled if the menu is set to 6 This percentage will help determine when switching back to heat pump only operation is appropriate Default 20 If target time 20 minu...

Страница 30: ...range selected in the COOL RPS RANGE menu Select the appropriate compressor RPS for the installed system configuration SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS HT Reset YES or NO Selecting to def...

Страница 31: ...ating status will not be shown in the thermostat status menu or on the outdoor 7 segment displays The 7 segment displays on indoor control board will display EE 1 HEATING EMERGENCY MODE Emergency Heat...

Страница 32: ...15 ON OFF ON ON Sixth X 19 20 20 ON OFF ON OFF Seventh X X X 25 ON OFF OFF ON Switch Bank DS 3 Indoor Control Board Settings Heater Kit Selection Heater kW Dip Switch Setting NOTE Default factory sett...

Страница 33: ...el 8 minutes 10 minutes 50 High Cool Level 15 minutes 6 minutes 70 NOTE This mode does not require a thermostat Any thermostat requests will be ignored while in emergency operation NOTE Set indoor DS...

Страница 34: ...Enable 16 OFF No Use 17 ON Emergency EEV Opening 18 OFF Emergency EEV Opening 19 OFF EEV Emergency Mode 20 OFF No Use 21 OFF Emergency mode Cooling and Hea ng Emergency Mode 22 OFF Emergency mode Cool...

Страница 35: ...sponding Screen within the display itself which allows the user to navigate and use the features Example The Fault Code is accessed and displayed from Screen 0 of the 7 segment display The Fault Histo...

Страница 36: ...t fault To access hold the RECALL button for 5 seconds at screen 0 To access hold the RECALL button for 5 seconds at screen 1 To access hold the RECALL button To access hold the RECALL and TEST button...

Страница 37: ...allow the user to see the six most recent system faults For a list of the fault codes please see the TROUBLESHOOTING tables in this document 1 SCREEN 0 SCREEN 1 The display will change to SCREEN 1 Di...

Страница 38: ...Press RECALL Item number Display flickers at 1 second intervals Value MONITORING MODE NAVIGATION SCR This screen allows the user to monitor system variables as shown in the tables at the end of this s...

Страница 39: ...n in the tables at the end of this section SCREEN 0 Press RECALL Press RECALL to increase the value Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode...

Страница 40: ...CALL Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode Press RECALL Press RECALL Press RECALL SCREEN 0 OFF ON Blink interval 0 4 sec On 0 4 sec Off Pr...

Страница 41: ...tart up 3 Oil Return Operation 4 Heating Operation 5 Defrost Operation 6 Cooling Operation 3 Compressor Reduction Mode 0 OFF 1 ON 4 demand unit Cut off the decimal first place 5 act demand unit Cut of...

Страница 42: ...12 4 3 10 15 5 0 4 Cool Profile 0 A 2 C 1 B 3 D 5 Cool ON Delay 0 5sec 2 20sec 1 10sec 3 30sec 6 Cool OFF Delay 0 30sec 2 90sec 1 60sec 3 120sec 7 Dehumidfication Select 0 ON 1 OFF 8 Heat Airflow Trim...

Страница 43: ...oor Lower 2 Indoor Lower 4 System Verification Test 0 ON 1 OFF 7 Force Defrost Cycle 0 ON 1 OFF 8 Pump Down 0 ON 1 OFF 9 Charge Mode 0 ON 1 OFF 10 Maximum Compressor RPS for Cooling 11 Maximum Compres...

Страница 44: ...er X X X X X X Outdoor Ambient temp is too high X X X X X X Outdoor Ambient temp is too low X X X X X X X X X X ID suction temp is too high X X X X X ID suction temp is too low X X X Mixture of non co...

Страница 45: ...X Outdoor Ambient temp is too low X X X X X X X X X ID suction temp is too high X X ID suction temp is too low X X X X X X X X X Mixture of non condensible gas X X X X X X X X X X OD fan motor failur...

Страница 46: ...w pressure faults Control has determined continued operation is acceptable This indicates they may be a problem with the equipment Stop valve not completely open Restriction in refrigerant lines Low r...

Страница 47: ...Faulty control board Noise Check wiring to control board Repair as needed Replace control board if necessary 32 E32 HI TEMP CTRL1 This error indicates the equipment is experiencing high temperature fa...

Страница 48: ...o power supply as specified on rating plate Correct low line voltage condition Contact local utility if needed 43 E43 HIGH LINE VOLT Control detects a high power supply voltage condition High line vol...

Страница 49: ...eeded Check the connection to thermistors Repair replace if needed B0 Eb0 NO ID AIRFLOW The estimated airflow from indoor subsystem is near to 0 CFM Failed indoor blower motor Indoor fan motor not pro...

Страница 50: ...rk traffic The table below indicates the LED status and the corre sponding potential problem LEARN button Used to reset the network Press the button for approximately 5 seconds to reset the network LE...

Страница 51: ...42 13 04 1 42 147 37 3 95 13 07 1 42 40 104 10 63 1 22 10 63 1 22 118 68 3 76 10 65 1 22 45 113 8 71 1 04 8 71 1 04 96 13 3 56 8 73 1 05 50 122 7 18 0 89 7 18 0 89 78 29 3 34 7 18 0 89 55 131 5 95 0...

Страница 52: ...128 7 596 148 4 60 8 6 162 57 0 264 87 4 366 110 4 468 0 129 0 600 149 0 62 10 0 164 57 7 266 87 9 368 110 8 470 0 129 3 604 149 5 64 11 3 166 58 4 268 88 4 370 111 2 472 0 129 7 608 150 1 66 12 6 168...

Страница 53: ...299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96...

Страница 54: ...ide the sheet metal plate with the electrical board behind the refrigerant tubing as shown PCB MOUNTING PLATE PCB SLIDE RAIL PCB ASSY INSTALL THE ELECTRICAL BOARD When working on a service port ensure...

Страница 55: ...E THE STATIC ELECTRICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHAR...

Страница 56: ...E THE STATIC ELECTRICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHAR...

Страница 57: ...COLOR AMBIENT THERMISTOR SUCTION GR LINE DISCHARGE LIQUID LINE DEFROST COIL CIRCUIT SEG1 SEG2 SEG3 TO TSTAT OR INDOOR UNIT FIELD WIRING SEE NOTE 3 208 230 V 60 HZ NOTES 1 THE POSITION OF THE SELECTOR...

Страница 58: ...2 WIRE SELECTOR SWITCH DS1 DS6 DS6 X1A X3A X15A BS2 X5A X2A BS1 SEG2 SEG1 DS1 DS2 DS3 DS4 DS5 X7A X12A X13A RX LED X8A INDOOR UNIT PCB THERMISTOR HEAT EXCHANGER 1 2 INTEGRATION TYPE MPU CPU LED STATU...

Страница 59: ...ANDBY NO THERMOSTAT INPUTS 6 YELLOW STATUS LED PROVIDES NETWORK STATUS GREEN RX LED INDICATES NETWORK TRAFFIC 7 DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT 8 REMOVE SHORTING PLATE FROM THE...

Страница 60: ...et up menu on the thermostat and DIP switch on indoor unit control board For more information please see indoor unit I O manual For match up with a 2 ton outdoor unit Heater kit application shall not...

Страница 61: ...A minimum of field wiring is required to complete the installation Other components such as a Heating Cooling Thermostat and Outdoor Thermostats are available to complete the installation The system...

Страница 62: ...0 23800 32400 48600 66500 71600 ELECTRIC HEATER CAPACITY BTUH FORMULAS Heating Output KW x 3 413 x Corr Factor Actual CFM CFM from table x Corr Factor BTUH KW x 3 413 BTUH CFM x 1 08 x Temperature Ris...

Страница 63: ...contact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN B...

Отзывы: