REMARK: J:RELAY R:HEATING SYSTEM T:TRIAC
THERMAL CUT-OUT 194º F
MS210C2T_U
MS240C2T_U
MS270C2T_U
L1
L1'
L1"
L2"
E
OUTLET TEMP.SENSOR
L2
L2'
T1
T2
T3
R1
R2
R3
CONTROL
SYSTEM
DISPLAY
SCREEN
INLET TEMP.SENSOR
FLOWMETER
MS210C2T_U MS240C2T_U MS270C2T_U
E L1 L2 L1 L2 L1 L2
Bottom case
Control board
Display screen
Terminal blocks
Flowmeter
Temp.sensor
Heating chamber
Display screen
UP
ON/OFF
DOWN
WIRE CONNECTIONS TO BREAKERS
E / G
L1
L2
L1
L2
L1
L2
Double Pole Breaker
40 A MS210
40 A MS240
50 A MS270
Double Pole Breaker
40 A MS210
40 A MS240
50 A MS270
Double Pole Breaker
40 A MS210
40 A MS240
50 A MS270
11 in
16.14 in
B-3. MS210C2T_U, MS240C2T_U, & MS270C2T_U must be connected to three double pole breaker.
Read all name plates carefully and wire as per instructions, and tables 2 and 3.
14
Fig 14
Fig 15
Wiring Diagram