3.

Installing the PS4350

3.1 Unpacking

The PS4350/R package includes the following parts:

• One beige PC4055C cabinet OR one red PC4055CR

cabinet (15.0”H x 15.0”W x 6.9”D)

• One PS4085 charger module
• One PT1012 transformer, 16 Vac, 80VA
• Space for one 20-60Ah, 12 volt sealed lead-acid

battery (not included)

3.2 Mounting the Cabinet

When mounting the cabinet for the PS4350/R, select a dry
location within 1m/3.3ft of the control panel.

To mount the cabinet you will need:

• six - #10x2½” round head, steel wood-screws (not

supplied)

• six - #10x¾” round head, steel wood-screws (not

supplied)

• one - 20”x20”x¾” sheet of plywood (not supplied)
• screwdriver (not supplied)
• stud finder (not supplied)

To mount the cabinet:

1. Using the stud finder, find a

mounting location where the
plywood sheet can be
mounted to 2 different studs,
as shown .

When mounting the
plywood, ensure that the
bottom of the cabinet will not
be less than 16” and not
more than 48” from the floor.

2. Attach the plywood to the

wall using the six #10x2½”
round head steel screws.

3. From the back of the cabinet,

press in the four white
circuit board stand-offs into
the raised mounting holes.

4. Holding the cabinet in

position, pull all wiring into
the cabinet through the hole
in the back.

5. Using the six  #10x¾” round

head steel screws, mount the
cabinet securely to the
plywood sheet, as shown.

6. Press the PS4085 module onto the plastic stand-offs.

3.3 Wiring

Before beginning to wire the unit, ensure that all power
(AC transformer and battery) is disconnected from the
control panel.

Consult the wiring diagram on the previous page for
instructions.

A minimum of ¼” (7mm) separation must be maintained
at all points between power limited wiring and all other
non-power limited wiring and connections. Wire entry for
power limited wiring must be separate from non-power
limited wiring.

3.4 Applying Power

After all wiring is completed, apply power to the control
panel. Connect the battery leads to the battery, then connect
the AC transformer. For more information on control panel
power specifications, see the control panel Installation
Manual.

NOTE: 

Do not connect the power until all wiring is

complete.