background image

Page

 

3

 

of

 

3

 

Basic Control Remote - Quick Guide

 

Phone: 1-800-555-5629

Fax: 973-244-7333

Web: www.maxlite.com

E-mail: [email protected]

Rev: 04/06/21

© 2021 Specifications subject to change without notice.

HOLD TIME

2 Seconds

STANDBY DIM

50%

STANDBY TIME

2 Seconds

Default settings can be changed during commissioning

For Standby Dim, “0%” means on/off control. There is no standby dimming level. 

For Standby time “

” means bi-level dimming control. Luminaire will never turn off.

Memory Mode (Commissioning)

To begin commissioning, follow the steps below:

1. Select either M1, M2, M3, or M4. 

2. Indicator lights on the remote will illuminate to indicate the 

    current saved settings.   

 

 

 

3. Settings can be changed by pressing appropriate buttons 

    in the highlighted gray area of the remote. (HIGH, SENSITIVITY, 

    HOLD TIME, STANDBY DIM, STANDBY TIME, and PHOTOCELL). 

    Review selected settings and make changes as necessary.  

 

4. Point remote to desired luminaire to commission and press “SEND”.

5. If configuration is successful, luminaire will flash suggesting settings 

    are saved. 

  

 

Note that any changes made to the sensor settings are automatically 

saved to the memory banks M1, M2, M3 or M4 and will override previous 

settings. 

If commissioning multiple luminaires, select the configured memory 

mode M1/M2/M3/M4 then follow steps 4 and 5.  

Test Mode

Press “TEST” to enter test mode. Luminaire will flash two times. 

Test mode will last five (5) minutes then return to previous setting.

To Turn Lights ON

Press “ON” to turn luminaire on.  

To Turn Lights OFF

Press “OFF” to turn luminaire off.

Manual Dimming Mode 

Press “ON”, luminaire will blink, then press DIM+ or DIM- to adjust 

dimming level.

Continuous Adjustment Mode or CAM

(Daylight Harvesting)

Continuously adjusts dim levels in response to changes in ambient light.
1. Point IR remote to desired luminaire 

2. Enter Manual Dimming Mode - Press “ON”, luminaire will blink,  

    then press DIM+ or DIM- to adjust the desired light level.

3. Press “CAM”, indicator lights on the remote will indicate current  

    saved settings. Note: only HIGH, SENSITIVITY, and HOLD TIME 

    can be selected for CAM settings. (Sensitivity should be set to 

    either LOW or HIGH) CAM feature recommended with CN-RTPSW  

    sensor only.

4. Review selected settings and make changes as necessary.  

    Press “SEND”.

5. If configuration is successful, luminaire will blink to confirm

    setting saved. 

If configurating multiple luminaires, repeat steps

 

1-5 above to configure CAM settings. Light levels 

 

has to be configured for each luminaire individually.

Reset Mode

Press “RESET” to enter reset mode. Luminaire will blink to indicate  

reset is complete. Sensor will default to original settings shown in the 

above table. 

Remote Settings

FEATURE

DEFINITION

SETTINGS

HIGH MODE

Set High Trim or Maximum light output setting

SET MAXIMUM THRESHOLD VALUE 50/75/100%.

(SENSOR DEFAULT = 100%)

SENSITIVITY

Set motion detection sensitivity

OFF (NO OCCUPANCY) / LOW (50%) / HIGH (100%)

(SENSOR DEFAULT=HIGH)

HOLD TIME

Time luminaire stays at the High Trim threshold when no 

motion detected before going into Standby Dim level.

30S/5M/15M/30M

(SENSOR DEFAULT=5MIN)

STANDBY DIM

With no motion detected and hold time elapsed, 

light output is reduced to this level

0/10/30/50% (SENSOR DEFAULT=50%)

STANDBY TIME

With no motion detected, length of time luminaire stays

at the Standby Dim level before turning OFF.

10S / 5MIN / 15MIN / 30MIN / 60MIN / 

(SENSOR DEFAULT=30MIN)

PHOTOCELL

Turns luminaire ON/OFF based on photosensor settings.

(Outdoor application)

LOW(1FC) / MEDIUM(20FC) / HIGH(50FC)  

(SENSOR DEFAULT = PC OFF)

PR

ELI

M

IN

AR

Y

Check out the 

remote commissioning 

video here.

Отзывы: