5–5
PARAMETERS
www.maxcessintl.com
MAGPOWR DTR-65
MI 850A349 1 D
Miscellaneous
Parameter # Description
Default
P.19
Tension number format
Tells whether tension display is 3-digit with no fixed right-
hand zero or 3-digit with fixed right-hand zero.
0
0 =
Auto Select between formats. (Based on value in
Maximum Tension C1.3 or C2.5).
1 = 3-digit with no fixed right-hand zero.
2 = 3-digit with fixed right-hand zero.
P.20
Tension polarity
Set to -1 to show positive tension when the force is acting in
the direction opposite the force direction arrow on the load
cells. Set automatically by Precision calibration.
+1
P.21
DP position
Set the decimal point position to show when displaying
tension
0
0 = 0000
1 = 0000.
2 = 000.0
3 = 00.00
4 = 0.000
P.22
Lock out zeroing tension from [
] button and digital input
when a password has locked the DLCA.
0
0 =
Zeroing tension allowed when password has locked the
DLCA
1 =
Zeroing tension locked out when password has locked
the DLCA
P.23
Firmware Version. Displays the firmware version.
P.24
Exit from menu and return to displaying tension