![MAXA HWA1 0140 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/maxa/hwa1-0140/hwa1-0140_userand-installers-manual_1743098022.webp)
HWA1-A & HWA1-H
Air/Water chillers and heat pumps with axial fans
22
12
DISPOSAL PROCEDURE
Once the unit comes to the end of its life cycle and needs to be removed or replaced, the following operations are recommended:
• the refrigerant has to be recovered by trained people and sent to proper collecting centre;
• the compressors’ lubricating oil has to be collected and sent to proper collecting centre;
• the frame and the various components, if not serviceable any longer, have to be dismantled and divided according to their
nature, particularly copper and aluminium, which are present in conspicuous quantity in the unit. These operations allow easy
material recover and recycling process, thus reducing the environmental impact.
13
TECHNICAL DATA
13.1
COOLING ONLY VERSION “HWA1-A”
TECHNICAL CHARACTERISTICS
Unit
Model HWA1-A
0140
0147
0260
0272
0285
Electric data
Power supply
400V/3P+N+T/50Hz
Maximum power input
kW
17
21,5
28
35
43
Maximum starting current
A
93
202
162
184
240
Maximum current input
A
28
38
45
56
71
Cooling
Cooling capacity (1)
kW
44,60
51,04
70,41
89,24
100,59
Power input (1)
kW
11,90
15,06
19,21
24,26
29,44
EER (1)
W/W
3,75
3,39
3,66
3,68
3,42
Cooling capacity (2)
kW
39,31
46,28
59,74
72,55
84,72
Power input (2)
kW
12,38
14,95
19,74
23,87
27,84
EER (2)
W/W
3,18
3,10
3,03
3,04
3,04
SEER (5)
W/W
3,18
3,25
3,84
3,62
3,74
Free cooling water temp.
from 15° to 10°C (4)
Cooling capacity air temp. at 0°C
kW
35,80
39,80
52,70
71,60
79,60
Cooling capacity air temp. at -5°C
kW
44,60
48,60
71,80
89,20
97,20
Desuperheater air at 35°C
water at 7°C (6)
Heating capacity water temp. 55°C
kW
11,30
13,22
17,92
22,70
26,01
Heating capacity water temp. 45°C
kW
13,56
15,86
21,51
27,24
31,21
Total recovery
Air at 35°C water at 7°C (6)
Heating capacity water temp. 55°C
kW
39,06
41,56
60,51
75,78
83,37
Heating capacity water temp. 45°C
kW
40,53
44,37
62,97
78,63
89,14
Compressor
Brand
Bitzer
Type
D6 Scroll
Number
1
2
Oil (type, quantity)
dm³
BVC32 / 2,7
BVC32 / 5,4
AC fan motor or Y/Δ,
for the model 0281
only for EC fan motor is
available for EC data see the
“H” version
Type
AC
EC
Number
1
Nominal capacity
kW
1,8
2,2
2,3
2,5
2,3
Power input Y / Δ (max)
kW
0,8 / 1,3
0,9 / 1,4
1,0 / 1,5
1,1 / 1,7
2,55
Current input Y / Δ (max)
A
1,5 / 2,7
1,7 / 3,0
1,8 / 3,2
2,1 / 3,7
3,9
Nominal air flow rate
m
3
/s
4,03
4,58
6,11
6,67
7,92
Refrigerant
Type
R 410 A
Refrigerant quantity
kg
7,7
7,8
12,0
12,2
12,3
Design pressure (High/low)
MPa
4,2/2,7
Hydraulic circuit
Water flow rate (2)
L/s
1,88
2,21
2,85
3,47
4,05
Available head pressure (2)
kPa
75,7
73,4
64,5
73,4
64,7
Internal head loss (2)
kPa
55,8
56,6
61,5
63,7
66,6
Pump rated power input (2)
kW
0,9
1,2
Pump max power input
kW
1,1
1,3
Pump max current input
A
2,4
2,6
Internal storage capacity
Litres
180
Hydraulic connections
Inch
2"
Minimum water volume of plant (7)
L
300
340
150
170
180
AC fan motor noise level
Sound power (8)
dB(A)
76,5
76,5
78
78
78 (fan EC)
Dimensions and weight
Dimensions (L×H×W)
mm
1170 x 1985 x 1 125
1170 x 2035 x 1125
Max. Packing dimensions (L×H×W)
mm
1200 x 2110 x 1150
1200 x 2170 x 1150
Operating weight
kg
350
360
455
480
495
Weight for transportation
kg
365
375
470
495
510
Operating conditions:
(1) Cooling:
Outdoor air temperature 35°C; inlet/outlet water temperature 23/18°C.
(2) Cooling:
Outdoor air temperature 35°C; inlet/outlet water temperature 12/7°C.
(3) Heating:
Outdoor air temperature 7°C DB 6°C WB; inlet/outlet water temperature 30/35°C.
(4)
Cooling:
accessory supplied only with EC brushless fan motor
(5) Cooling:
accessory supplied only with EC brushless circulator
(6) Cooling:
accessory supplied only with EC brushless circulator
(7) Switch
off/
Switch on
inertia: calculated for a ΔT=10°C max (in 6/3 minutes of mono/bi-compressor stop)
(8) Sound power cooling mode; value determined on the basis of measurements taken in accordance with the UNI EN ISO 9614-2, in compliance with the
requirements of Eurovent certification.
N.B. The performancee data are indicative and could be subject to change.